NC-485X Network Converter
Application Note
Page 5 of 13
P/N: 01967-001 Rev. C
Figure 4: Telnet Configuration Main Window
3. Press 2 <Enter> to enter the Channel 2 Configuration values. The second configuration parameter
is displayed.
4. If a configuration value needs to be changed, type the new value and the original value is
overwritten. Every time <Enter> is pressed, the displayed configuration value is accepted and the
next parameter is displayed.
5. Press <Enter> until the I/F Mode parameter is displayed. This value must be
4F
for proper
communication between LAN-520Xs over RS-485. If this value is not
4F
, type
4F
to overwrite
the original value.
6. Press <Enter> until the Port parameter is displayed. This value must be
10002
for proper
communication between
Doors
and the LAN-520X. If this value is not
10002
, type
10002
to
overwrite the original value.
NOTE: This value should not be changed unless multiple PXL networks are on the same LAN Subnet
(see “Using Multiple PXL Networks on the Same LAN Subnet” on page 9) or instructed to do so by
either Keri Systems or Lantronix Technical Support Staff.
7. Press <Enter> until the Connect Mode parameter is displayed. The default for this value is
0C
. If
all LAN-520X units are within the local subnet, leave the default as is. If one or more LAN-
520Xs are located outside the local subnet, this value must be overwritten to
2C
for Master
controllers to enable use of Hostlist.
8. Press <Enter> until the Remote IP Address parameter is displayed. Setting the remote IP address
will designate this unit as a slave. Leave it at the default (0.0.0.0).