NC-485X Network Converter

Application Note

Page 12 of 13

P/N: 01967-001 Rev. C

Master PXL is 
unable to 
communicate to 
a single Slave 
PXL connected 
via Ethernet.

The J103 lead on the 
Slave’s NC-485X is 
reversed.

Remote IP address or 
Port number does not 
match the LAN-520X 
Master Port number.

IP Address is not 
reachable from the 
Master LAN-520X to 
the Slave LAN-520X.

If communicating to a 
unit outside the 
network subnet, the 
Gateway IP Address is 
not set in the LAN-
520X Master or Slave.

Verify Pin 1 on the J103 connector lead is 
connected to Pin 1 on JP-9 on the PXL.

Verify the IP Address and Port number of the 
LAN-520X Master matches the Remote IP 
address and Port number on the slaves. The 
default Port number for Channel 2 is 10002.

IP Address, routing, or subnet mask may be 
incorrect. Consult Network Administrator.

Enter the Gateway IP Address in the Server 
Properties of the LAN-520X (may be Master 
or Slave).

Master PXL is 
unable to 
communicate to 
any Slave PXL.

J103 lead on the 
Master’s NC-485X 
reversed.

The Remote IP 
Address or Port 
number does not match 
the LAN-520X Master 
Port number.

IP Address is not 
reachable.

Verify Pin 1 on the J102 connector lead is 
connected to Pin 1 on JP-9 on the PXL.

Verify the IP Address and Port number of the 
LAN-520X Master matches the Remote IP 
address and Port number on the slaves. The 
default Port number for Channel 2 is 10002.

IP Address, routing, or subnet mask may be 
incorrect. Consult Network Administrator.

Communication 
errors are 
received in 
Doors during an 
Update Net, 
Collect Events, 
or Event 
Monitoring.

High latency or low 
bandwidth is causing 
the PXL Master to time 
out waiting on a 
response from the PXL 
Slave.

Ping time should be under 300ms for optimal 
communication. If not, consult Network 
Administrator.

Problem

Possible Reason

Possible Solution

Содержание NC-485X

Страница 1: ...al using the LAN 520X with a NC 485X provides the ability to have Slave PXLs located throughout the world managed from one central location NOTE If all network segments are not located within the same...

Страница 2: ...twork segments can be connected to a PXL Master It is also possible to connect a PXL network outside of the Local LAN by utilizing a VPN or WAN Figure 1 Single Site with Multiple Network Segments 3 0...

Страница 3: ...be configured in Master mode Only one LAN 520X Master can exist in a PXL network All other LAN 520X units within a PXL network must be configured in Slave mode This document assumes that Channel 1 of...

Страница 4: ...e two ways to open Telnet through the Lantronix DeviceInstaller window or by opening a DOS box From the DeviceInstaller page locate and double click on the IP address of the LAN 520X Select the Telnet...

Страница 5: ...isplayed This value must be 10002 for proper communication between Doors and the LAN 520X If this value is not 10002 type 10002 to overwrite the original value NOTE This value should not be changed un...

Страница 6: ...nd Port number for each slave unit The Port number should be set to 10002 11 Once all the IP addresses and Port numbers have been entered enter an IP address of 0 0 0 0 to exit and press N when the Ch...

Страница 7: ...ress Enter simply click the box again to establish a connection to Telnet 2 Once Telnet connects with the LAN 520X all current configuration information is displayed and the cursor is placed at the Yo...

Страница 8: ...are on the same LAN Subnet see Using Multiple PXL Networks on the Same LAN Subnet on page 9 or instructed to do so by either Keri Systems or Lantronix Technical Support Staff 9 Press Enter until the C...

Страница 9: ...ort number For each PXL Network change the Channel 2 Port setting on the LAN 520X Master and Slaves to a unique number It is recommended that the port number be incremented by one digit for each netwo...

Страница 10: ...ion Settings on page 4 4 2 Verify the LAN 520X is Online 1 Ping the IP address of the LAN 520X If the ping fails that means a communication connection cannot be made Possible reasons are There is no p...

Страница 11: ...X LAN connection is the problem then only that LAN 520X will have LEDs 1 2 and 4 solid NC 485X Cable Connected LED 1 2 4 Solid LED 2 Blinking LED 1 4 Solid LED 2 Blinking NC 485X Cable Not Connected P...

Страница 12: ...ork Administrator Enter the Gateway IP Address in the Server Properties of the LAN 520X may be Master or Slave Master PXL is unable to communicate to any Slave PXL J103 lead on the Master s NC 485X re...

Страница 13: ...System s installation of the Device Installer has a modified version of the Lantronix device list Update the list by modifying the ProductInfobase txt file in the Lantronix DeviceInstaller folder to...

Отзывы: