loc
- LOCK; This section of the program menu sets up the lockout type and code.
LC ALL
- LOCK ALL; When this is selected the lockout will lock the program as well as the Presets and reset
button. The presets can be viewed but not changed.
lc pg
- LOCK PROGRAM; When this is selected the lockout will lock only the program. The Reset can be
activated and the presets can be viewed and changed.
code
- CODE; This is a 5-digit code which will be used to lock and unlock the front panel.
setup
- SETUP; This section of the program menu sets up the operating variables.
rdec
- RATE DECIMAL LOCATION; This allows the user to program a decimal point for the rate display.
SET Hi
- SET HIGH; This is the rate value for the highest input (5 or 10 Volts; 20 mA). (i.e. 20 mA = 500 lbs/
hr.)
lo cut
- LOW CUT-OFF; This is the lowest rate value to be recognized. All rate readings below this value will
assume the "set lo" value.
nor
- NORMALIZING FACTOR; This is an averaging factor (00.0 to 99.9). Higher settings provide more nor-
malizing (averaging) for a more stable display. Derived from the equation:
(OLD DATA x "NOR" + NEW DATA)
(OLD DATA x "NOR" + NEW DATA)
("NOR" + 1)
Sec
- SECONDS; This tells the unit that the High input value is entered in units per second.
NNiNs
- MINUTES; This tells the unit that the High input value is entered in units per minute.
hours
- HOURS; This tells the unit that the High input value is entered in units per hour.
days
- DAYS; This tells the unit that the High input value is entered in units per day.
tdec
- TOTALIZER DECIMAL LOCATION; This allows the user to enter a decimal for the totalizer display.
This decimal is not a dummy decimal and will scale the totalizer display accordingly. (i.e. if the tdec is set
in the tenths position (#####.#), 100 will be displayed as 100.0)
cfdec
- CONVERSION FACTOR DECIMAL; This menu allows users to select a decimal location for the con-
version factor
cfac
- CONVERSION FACTOR; This is a conversion divider factor that will be applied to convert from rate
volume units to total volume units (i.e. rate is gal/(units time) to ft
3
Conversion factor = 7.4805 (gal/ft
3
).