MIX 04 (694 444 64)
Kendrion Kuhnke Automation GmbH
130
17 May 2021
Bit
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
Error Register
Error Origin
Sub-Number
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Error Code
Error Register [31 … 24]
Copy of object 0x1001 after triggering the error
Error Origin [23 … 20]
Error source in the device
0xF
Module / Logical Device overlapping
0x1
Encoder 1
0x2
Encoder 2
0x3
AI/AO
Sub-
Number [19 … 16]
See table Error Code
Error Code [15 … 0]
Errorcode Sub Device
Channel Reaction
Explanation
0x2110
0x0
Enc1/Enc2
No
Overcurrent supply encoder
0x2320
0x0
AI/AO
AO0
Output is set to zero
Overtemperature output driver
0x2320
0x1
AI/AO
AO1
Output is set to zero
Overtemperature output driver
0x2320
0x2
AI/AO
AO2
Output is set to zero
Overtemperature output driver
0x2320
0x3
AI/AO
AO3
Output is set to zero
Overtemperature output driver
0x2330
0x0
AI/AO
AO0
Output is set to zero
Open Circuit / Overvoltage
0x2330
0x1
AI/AO
AO1
Output is set to zero
Open Circuit / Overvoltage
0x2330
0x2
AI/AO
AO2
Output is set to zero
Open Circuit / Overvoltage
0x2330
0x3
AI/AO
AO3
Output is set to zero
Open Circuit / Overvoltage
0x3100
0x0
Modul
No
Undervoltage module
0x3110
0x1
Enc1/Enc2
No
Signal integrity error
0x5030
0x0
AI/AO
AI0
No
Current lower than 4mA
0x5030
0xA AI/AO
AI0
No
Input outside parametrized limits
0x5030
0x1
AI/AO
AI1
No
Current lower than 4mA
0x5030
0xB AI/AO
AI1
No
Input outside parametrized limits
0x5030
0x2
AI/AO
AI2
No
Current lower than 4mA
0x5030
0xC AI/AO
AI2
No
Input outside parametrized limits
0x5030
0x3
AI/AO
AI3
No
Current lower than 4mA
0x5030
0xD AI/AO
AI3
No
Input outside parametrized limits
0x6100
0x0
Modul
Device no longer in
Operational
Watchdog
0x7000
0x0
Enc1/Enc2
No
CRC-error EnDat
0x7000
0x1
Enc1/Enc2
No
Encoder error EnDat
0x7000
0x2
Enc1/Enc2
No
Timeout/Answer Format EnDat
0x8100
0x0
Modul
Device no longer in
Operational
Communication error