Kendrion Kuhnke Automation GmbH
Mix 04 (694 444 64)
127
17 May 2021
Object dictionary
The Kuhnke FIO MIX 04 is divided into 3 virtual devices. The objects are structured as follows
0x1000 … 0x1FFF
Device specific
0x2000 … 0x23FF
Manufacture specific: Counter / Encoder 1
0x2800 … 0x2FFF
Manufacture specific: Counter / Encoder 2
0x3000 … 0x37FF
Manufacture specific: Analogue Input / Output
0x6000 … 0x67FF
Virtual Device: Counter / Encoder 1
0x6800 … 0x6FFF
Virtual Device: Counter / Encoder 2
0x7000 … 0x7FFF
Virtual Device: Analogue Input / Output
0x1000 Device type
Object Code
Variable
Sub
0x00
Name
Device type
Data Type
UNSIGNED32
Access
ro
Defaultvalue
5001 (0x1389)
PDO Mapping
No
5001 = Modular Device Profile
0x1001 Error register
Object Code
Variable
Sub
0x00
Name
Error register
Data Type
UNSIGNED8
Access
ro
Defaultvalue
PDO Mapping
no
In the case of an error, the corresponding error bit is set. If the error no longer exists, it is automatically
deleted.
In this object, the following objects are ORed together:
0x2001 Enc1 Error Register
0x2801 Enc2 Error Register
0x3001 AI/AO Error Register
7
6
5
4
3
2
1
0
MAN
RES
PROF
COM
TEMP
VOL
CUR
GEN
GEN: General error
CUR: Current
VOL: Voltage
TEMP: Temperature