K410062000000-00 / 05.2017
16
5.1.8 Operating mode: „Timer protection “, 16 water cut-off and opening times
The operating mode is operational as soon as timer times are stored in the "Timer
protection" menu
. Every timer from 1 to 16 can be allocated a
cut-off time or an opening time
.
Now select the day of the week when the switching operation is to occur.
Caution!
Always allocate a cut-off time and an opening time!!
An Isolation ball valve with servo drive is stipulated as standard!!
When using spring drives, set under:
System parameter >Safety valve
>Spring drive 230V
Example for settings:
Protection during absence for doctor’s offices, business, company buildings, etc.
Weekday Mo - Fr: Cut-off time: 8 pm, Opening time 8 am
Weekend Sa - Su: Protected except during cleaning on Sa 10 am – 12 pm
Timer01 / Closed / Time: 20:00:00 / Mo, Tu, We, Th, Fr, _ _
Timer02 / Open / Time: 08:00:00 / Mo, Tu, We, Th, Fr, _ _
Timer03 / Open / Time: 10:00:00 / _ _ _ _ _ Sa
Timer04 / Closed / Time: 12:00:00 / _ _ _ _ _ Sa
5.1.9 Operating mode: „Flush“ 16 possible water exchange intervals
The operating mode is operational as soon as a timer time is stored in the "Flush" menu. Every timer
from 1 to 16 can be allocated a time and a duration. Subsequently the weekdays are selected when
the switching operation is to occur.
Example: Timer01 / Active / Time: 08:00:00 / Mo _ We_ Fr _ Sa / Duration (min.): 5:00
Caution!
An Isolating ball valve with spring-reset is stipulated as standard!!
Содержание 620
Страница 14: ...K410062000000 00 05 2017 14 5 1 7 Systemparameter Sicherungsventil Spülventil ...
Страница 17: ...K410062000000 00 05 2017 17 5 1 11 Ablaufplan komplett ...
Страница 35: ...K410062000000 00 05 2017 15 5 1 7 Systemparameter ...
Страница 38: ...K410062000000 00 05 2017 18 5 1 11 Complete flowchart ...
Страница 54: ...K410062000000 00 05 2017 14 5 1 7 Systeemparameters ...
Страница 57: ...K410062000000 00 05 2017 17 5 1 11 Compleet stroomschema ...