K410062000000-00 / 05.2017
8
4.1
Assembly
4.1.1 Installing the leak controller
The leak controller is intended for wall installation. The housing has 4 each ø 4 mm mounting holes
in a clearance of w = 148 mm and h = 50 mm. To mount the cover, open the device and screw
tightly to the wall. After mounting the housing, make the required electrical connections.
4.1.2 Installing the water sensor
The water sensor is mounted on the floor or wall of the room to be protected by using the ø 4 mm
mounting hold.
4.1.3 Mounting the KHS Isolating valves
See separate installation and operating instructions, Figure 686 04, Figure 686 05 or 685 15
4.2
Electrical connection of leak controller, additional connection variants for
operational cases:
4.2.1 Terminal description:
1.
Safety valve – circuit output 230 V
8. Flush valve - N
2.
Safety valve – voltage output 230 V
9. External input 230 V (e.g. switch)
3.
Flush valve – circuit output 230 V
10. Protective earth conductor -PE
4.
Flush valve – voltage output 230 V
11. Water sensor 1 (wire confusable)
5.
Voltage supply (cable) - L1
12. Water sensor 2 (wire confusable)
6.
Voltage supply (cable) - N
13. Float switch (wire confusable)
7.
Safety valve - N
14. Alarm relay 230 V / 2A
max.
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Содержание 620
Страница 14: ...K410062000000 00 05 2017 14 5 1 7 Systemparameter Sicherungsventil Spülventil ...
Страница 17: ...K410062000000 00 05 2017 17 5 1 11 Ablaufplan komplett ...
Страница 35: ...K410062000000 00 05 2017 15 5 1 7 Systemparameter ...
Страница 38: ...K410062000000 00 05 2017 18 5 1 11 Complete flowchart ...
Страница 54: ...K410062000000 00 05 2017 14 5 1 7 Systeemparameters ...
Страница 57: ...K410062000000 00 05 2017 17 5 1 11 Compleet stroomschema ...