K410062000000-00 / 05.2017
5
•
Humidity: 0-90% non-condensing
•
Acoustic alarm (can be switched off)
•
Reset function for alarm hold: Acknowledge on device
•
Real-time clock (timing inaccuracy of the real-time clock < 1 min./year) with adjustable day
and week programs, automatic switchover between
daylight savings - standard time
•
Screwless cable terminals with operating lever
•
Manual valve operation on device
•
Relay protection valve switching capacity: max. 5A AC 1 / 230 V
•
Relay flush valve switching capacity: max. 5A AC 1 / 230 V
•
Floating alarm relay: max. 230 V, 2 A
•
Max. series fuse: 16 A
•
Potential number of KHS Isolating valves based on Illustration 2.1 (Item 1): 1 to 10 each
parallel operated via electrical sub distribution
•
Potential number of KHS Isolating valves based on Illustration 2.3 (Item 1): 1 pc
•
Max. lead length for water sensor: < 50 m with lead diameter min. 2x2x0.6 mm²,
> 50 m with lead diameter min. 2x0.75 mm², shielded wire
for example UL-LIYCY Apply shield one-sided to the PE
terminal, Pos. 10 in the control
1.3.2 Interfaces
•
Three inputs for water sensor, direct-current resistance measurement
•
One input adjustable for channel monitoring
•
Relay protection valve switching capacity: 5A AC1 / 230 V
•
Relay flush-valve switching capacity: 5A AC1 / 230 V
•
Floating alarm relay: max. 230 V, 2 A
•
230 V input for external switch or key switch, safety valve open/closed
1.3.3 Function | Software
•
The software queries the sensor inputs and switch inputs, controls the relay, reads and sets
the real-time clock (timing inaccuracy of the real-time clock < 1 min./year)
•
"Certainty" – Protection without water sensors, use of a closing system via a button
•
Menu-driven operation in German or English
•
The operating modes and the operating mode combinations are freely selectable
1.3.4 Operating modes
•
„Protection“
Leak monitoring with water sensors
•
„Protection + Timer“
Leak monitoring with the water sensors, 16 possible water cut-off
and opening times
•
„Flush“
16 possible flushing intervals
•
„Prot Flushing“
Leak monitoring with the water sensors, 16 possible water cut-off
and opening times
•
„Protection + Timer + Flushing“
Leak monitoring with the water sensors, 16 possible
water cut-off and opening times, 16 possible flushing intervals
•
„Not ready“
No parameters stored
Содержание 620
Страница 14: ...K410062000000 00 05 2017 14 5 1 7 Systemparameter Sicherungsventil Spülventil ...
Страница 17: ...K410062000000 00 05 2017 17 5 1 11 Ablaufplan komplett ...
Страница 35: ...K410062000000 00 05 2017 15 5 1 7 Systemparameter ...
Страница 38: ...K410062000000 00 05 2017 18 5 1 11 Complete flowchart ...
Страница 54: ...K410062000000 00 05 2017 14 5 1 7 Systeemparameters ...
Страница 57: ...K410062000000 00 05 2017 17 5 1 11 Compleet stroomschema ...