Kelvinator Air Conditioning

  installation  9

8  installation  

Kelvinator Air Conditioning

Upper Hook

Lower Hook

Cushioning
material

5.  Piping and wrapping

Bundle the tubing, connecting cable, and drain hose with 
tape securely and evenly as shown page 13.
•   Because the condensed water from rear of the indoor 

unit is gathered in the ponding box and is piped out of 
the room, do not put anything else in this box.

Connecting
pipe

Wrapping belt

Drain hose

Indoor unit

Ponding box

Pipe room

Connecting

cable

caution

•  Connect the indoor unit first, then the outdoor unit.
•   Do not allow the piping to be exposed out from the back 

of the indoor unit.

•  Be careful not to let the drain hose become slack.
•  Heat insulate the connecting piping.
•   Be sure that the drain hose is located at the lowest side 

of the bundle. Locating at the upper side can cause drain 
pan to overflow inside the unit.

•   Never cross connect or inter wind the power wire with 

any other wiring.

•   Run the drain hose sloped downward to drain out the 

condensed water smoothly. 

3.  Connecting Pipe and Drainage Installation

1   Run the drain hose sloping downward. Do not install the 

drain hose as illustrated below.

Do not block water flow with a rise.

Do not put the end of the 

drain hose into water.

2   When connecting an extension drain hose, insulate the 

connecting part of the extension drain hose with a shield 
pipe, do not let the drain hose become slack.

Connecting pipe

1   For the left-hand and right-hand piping, remove the pipe 

cover from the side panel.

2   For the rear-right-hand and rear-left-hand piping, install 

the piping as shown. Bend the connecting pipe to be laid 
at a height of 43mm or less from the wall.

3   Fix the end of the connecting pipe. (Refer to Tightening 

Connection in REFRIGERANT PIPING CONNECTION)

Right-hand piping

Side Part cover

Left-hand piping

Rear-right piping

Rear-left piping

.

.

.

.

.

.

.

. .

.

. .

.

.

.

.

. .

.

.

. .

.

.. .

.

.

. .

.

.. .

.

. .

.

.

.

.

.

.

.

.. .

.

.

. .

.

.

.

.

.

. .

.

. . .

..

.

.

.

.

. .

.

.

.

.

.

.

. .

.

.

.. ..

.

.

.

. .

.

.

.

. .

. .

.

.

.

.

. .

.

..

.

. .

.

.

.

.

.

. .

.

.

.

.

.

. .

.

.

.

.

.

.

.

.

.

.

. ..

.

.

.

.

.

.

.

......

..

.

.

.

.. .

4

3

Indoor unit outline Connecting pipe

Installation

Indoor

Outdoor

5

-7

m

m

Wall

(7.0kw) and (8.0kw) model)

A

40

B

Right rear side 

refrigerant

pipe hole  65

Installation plate

Indoor unit outline

Left rear side 

refrigerant

pipe hole  65

15cm or more to ceiling

12cm or more

to wall

12cm or more

to wall

( (3.5kw) model, 

)

<(6.2kw) model

<(3.5kw) model: (A: 710, B: 250/ A:790, B:265)

(3.5kw) model: (A: 790, B:265)

90

40

45

15cm or more to ceiling

Indoor unit outline

Installation plate

30

5

Right rear side 

refrigerant

pipe hole  65

Left rear side 

refrigerant

pipe hole  65

12cm or more

to wall

12cm or more

to wall

850

45

90

45

45

2

7

2

80

489

(>(6.2kw)model)

12cm or more 

 

to the wall

to the wall

12cm or more 

5

0

15cm or more to the ceiling

Indoor Unit Outline

380

Hooked Part

380

998

32

2

119

130

65

65

130

50

Above 12cm to

the wall

Above 12cm to

the wall

Above 15cm to    

the ceiling 

32

5

55

95

95

55

1250

815

257

178

55

58

Pipe hole

Hooked Part Hooker Part

Pipe hole

Indoor unit outline

Indoor

Outdoor

5

-7

m

m

Wall

(7.0kw) and (8.0kw) model)

A

40

B

Right rear side 

refrigerant

pipe hole  65

Installation plate

Indoor unit outline

Left rear side 

refrigerant

pipe hole  65

15cm or more to ceiling

12cm or more

to wall

12cm or more

to wall

( (3.5kw) model, 

)

<(6.2kw) model

<(3.5kw) model: (A: 710, B: 250/ A:790, B:265)

(3.5kw) model: (A: 790, B:265)

90

40

45

15cm or more to ceiling

Indoor unit outline

Installation plate

30

5

Right rear side 

refrigerant

pipe hole  65

Left rear side 

refrigerant

pipe hole  65

12cm or more

to wall

12cm or more

to wall

850

45

90

45

45

2

7

2

80

489

(>(6.2kw)model)

12cm or more 

 

to the wall

to the wall

12cm or more 

5

0

15cm or more to the ceiling

Indoor Unit Outline

380

Hooked Part

380

998

32

2

119

130

65

65

130

50

Above 12cm to

the wall

Above 12cm to

the wall

Above 15cm to    

the ceiling 

32

5

55

95

95

55

1250

815

257

178

55

58

Pipe hole

Hooked Part Hooker Part

Pipe hole

Indoor unit outline

2.  Drill a hole in the wall

 Determine  hole 
positions according to 
the diagram detailed in 
Fig.5. Drill one (1) hole 
( 65mm) slanting slightly 
to outdoor side.

2   Always use wall hole 

conduit when drilling 
metal grid, metal plate 
or the like.

Correct orientation  of Installation Plate

Indoor unit installation

1.  Fit the Installation Plate

1   Fit the installation plate horizontally on structural parts 

of the wall with spaces around the installation plate.

2   If the wall is made of brick, concrete or the like, drill eight 

(8) 5mm diameter holes in the wall. Insert Clip anchor for 
appropriate mounting screws.

3   Fit the installation plate on the wall with eight (8) type 

“A” screws.

Note:  Fit the Installation Plate and drill holes in the wall 

according to the wall structure and corresponding 
mounting points on the installation plate.

 

   (Dimensions are in “mm” unless otherwise stated)

4.  Indoor unit installation

1  Pass the piping through the hole in the wall.
2   Put the upper claw at the back of the indoor unit on 

the upper hook of the installation plate, move the indoor 
unit from side to side to see that it is securely hooked.

3   Piping can easily be made by lifting the indoor unit 

with a cushioning material between the indoor unit 
and the wall. Remove cushioning material after the 
piping is finished.

4   Push the lower part of the indoor unit up on the wall, 

Then move the indoor unit from side to side, up and 
down to check if it is hooked securely.

Содержание KSV26HRB

Страница 1: ...Inverter Split type Room Air Conditioner Installation Manual KSV26HRB KSV35HRB KSV53HRB KSV62HRB KSV70HRB KSV80HRB Refrigerant R410A ...

Страница 2: ...g the appliance tips and information This symbol indicates tips and information about use of the appliance environmental tip This symbol indicates tips and information about economical and ecological use of the appliance This symbol indicates never to do this This symbol indicates always do this Important safety instructions 2 Contents Kelvinator Air Conditioning Congratulations and thank you for ...

Страница 3: ...fied torque wrenches 1 8kgf m 4 2kgf m 5 5kgf m 6 6kgf m different depending on model No Spanner half union Hexagonal wrench 4mm Gas leak detector Vacuum pump Gauge manifold Users manual Thermometer Multimeter Pipe cutter Measuring tape Items required for installing the unit Number Name of Accessories Qty 1 Installation Plate 1 2 Clip Anchor 8 3 Self tapping Screw A 8 4 Seal See page 8 for details...

Страница 4: ... unit Make sure that condensation drainage can be conveniently routed away Do not install near a doorway Ensure that the space on the left and right of the unit is more than 12cm Use a stud finder to locate studs to prevent unnecessary damage to the wall The indoor unit should be installed on the wall at a height of 2 0m or more from the floor The indoor unit should be installed allowing a minimum...

Страница 5: ... pipe hole 65 Left rear side refrigerant pipe hole 65 12cm or more to wall 12cm or more to wall 850 45 90 45 45 272 80 489 6 2kw model 12cm or more to the wall to the wall 12cm or more 50 15cm or more to the ceiling Indoor Unit Outline 380 Hooked Part 380 998 322 119 130 65 65 130 50 Above 12cm to the wall Above 12cm to the wall Above 15cm to the ceiling 325 55 95 95 55 1250 815 257 178 55 58 Pipe...

Страница 6: ...ing of outdoor unit Anchor the outdoor unit with a bolt and nut 10 or 8 tightly and horizontally on a concrete or rigid mount Model A mm B mm 3 5kw 530 290 5 3kw 560 335 6 2kw 590 333 A B Air inlet Air outlet Air inlet Drain joint installation If a drain elbow is used the unit should be placed on a stand which is taller than 3cm If the unit is used in an area where temperature falls below 0O C for...

Страница 7: ...ing section C Tape the tubing drain hose and the connecting cable Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause drain pan to overflow inside the unit Note If the drain hose is routed inside the room insulate the hose with insulation material so that dripping from sweating condensation will not damage furniture or floors Foamed polyethy...

Страница 8: ...n screw Tubing retainer I Reroute the piping and the drain hose across the back of the chassis for rear left side external passage J Locating the indoor unit Remove the spacer Hook the indoor unit onto the upper portion of the installation plate Engage the hooks of the installation plate into the openings at the rear top of the indoor unit Ensure that the hooks are properly seated on the installat...

Страница 9: ...rcuit diagram posted on the inside of the control cover 2 The screws which fasten the wiring in the casing of electrical fittings may come loose from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could cause burn out of the wires 3 Specification of power source 4 Confirm that electrical...

Страница 10: ...an the atmosphere pressure 7 Remove the charge hose from the Low pressure charge hose 8 Fully open the packed valve stems B and A 9 Securely tighten the cap of the packed valve Manifold valve Compound meter 76cmHg Handle L o Handle Hi Charge hose Charge hose Vacuum pump Pressure gauge Low pressure valve Air purging Air purging Air and moisture in the refrigerant system have undesirable effects as ...

Страница 11: ...AUTO or COOL mode see User Manual for details The test operation should last about 30 minutes Manual control button AUTO COOL Rated Capacity Test Cooling mode Under Cooling Mode set the air conditioner at High Fan Speed and set the temperature to 17O C then press the TURBO button 6 times within 10 seconds be sure the indoor unit buzzes 6 times The system will enter Rated Capacity Test mode The buz...

Страница 12: ...rchase is required before you can make a claim under this warranty 7 You may not make a claim under this warranty unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse including failure to properly maintain or service iii normal wear and t...

Страница 13: ...rmation about Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web www kelvinator com au Kelvinator We are part of the Electrolux family Share more of our thinking at www electrolux com au ...

Отзывы: