Kelvinator KSV26HRB Скачать руководство пользователя страница 10

Kelvinator Air Conditioning

  air purging/test running  19

18  checking the drainage and forming piping/air purging  

Kelvinator Air Conditioning

Safety and leakage check

Electrical safety check

Perform the electrical safety check after completing 
the installation:
1  Grounding work
 

 After finishing grounding work, measure the grounding 
resistance by visual detection and grounding 
resistance tester.

2   Electrical leakage check (performing during test running)
 

 During test operation after finishing installation, the 
service person can use the electroprobe and multimeter 
to perform the electrical leakage check. Turn off the unit 
immediately if leakage happens. Check and find out the 
solution ways till the unit operates properly.

Gas leak check

1  Soap water method:
 

 Apply a soap water or a liquid neutral detergent on 
the indoor unit connection or outdoor unit connections 
by a soft brush to check for leakage of the connecting 
points of the piping. If bubbles come out, the pipes 
have leakage.

2. Leak detector
 

Use the leak detector to check for leakage.

caution

A  Lo packed valve
B  Hi packed valve
C and D are ends of indoor unit connection.

Indoor unit

check  point

D

B

C

A

Outdoor unit

check  point

Co

ver

Test running

Perform test operation after completing gas leak check at 
the flare nut connections and electrical safety check.
•   Check that all tubing and wiring have been properly 

connected.

•   Check that the gas and liquid side service valves are 

fully open.

•   Connect the power, press the ON/OFF button on the 

remote control to turn the unit on.

•   Use the MODE button to select COOL, HEAT, AUTO 

and FAN to check if all the functions work well.

Test running

When using the vacuum pump

(For method of using a manifold valve, refer to its 
operation manual.)
1   Completely tighten the flare nuts, A, B, C, D, connect 

the manifold valve charge hose to a charge port of the 
low-pressure valve on the gas pipe side.

2   Connect the charge hose connection to the 

vacuum pump.

3  Fully open the handle Lo of the manifold valve.
4   Operate the vacuum pump to evacuate. After starting 

evacuation, slightly loose the flare nut of the Lo valve 
on the gas pipe side and check that the air is entering

 

 (Operation noise of the vacuum pump changes and a 
compound meter indicates 0 instead of minus)

5   After the evacuation is complete, fully close the handle 

Lo of the manifold valve and stop the operation of the 
vacuum pump.

 

 Make evacuation for 15 minutes or more and check that 
the compound meter indicates -76cmHg (-1 x 10 Pa).

6   Turn the stem of the packed valve B about 45

o

 

counterclockwise for 6~7 seconds after the gas started 
coming out, then tighten the flare nut again. Make sure 
the pressure display in the pressure indicator is a little 
higher than the atmosphere pressure.

7   Remove the charge hose from the Low pressure 

charge hose.

8  Fully open the packed valve stems B and A.
9  Securely tighten the cap of the packed valve.

 

Manifold valve

C ompound meter

-76cmHg

Handle L o

Handle H i

C harge hose

C harge hose

Vacuum pump

P ressure gauge

Low pressure valv

e

Air purging

Air purging

Air and moisture in the refrigerant system have undesirable 
effects as indicated below:
•   Pressure in the system rises.
•   Operating current rises.
•   Cooling or heating efficiency drops.
•   Moisture in the refrigerant circuit may freeze and 

block capillary tubing.

•   Water may lead to corrosion of parts in the 

refrigeration system. 
Therefore, the indoor unit and tubing between the 
indoor and outdoor unit must be leak tested and 
evacuated to remove any noncondensables and 
moisture from the system.

Air purging with vacuum pump

•   Preparation 

Check that each tube (both liquid and gas side tubes) 
between the indoor and outdoor units have been 
properly connected and all wiring for the test run has 
been completed. Remove the service valve caps from 
both the gas and the liquid sides on the outdoor unit. 
Note that both the liquid and the gas side service valves 
on the outdoor unit are kept closed at this stage.

•   Pipe length and refrigerant amount:

Connecting 
pipe length

Air purging 

method

Additional amount of 

refrigerant to be charged

Less than 5m

Use vacuum 

pump

 –

More than 5m

Use vacuum 

pump

(2.6-5.3kw) Models: 

(Pipe length-5) x 20g/m

(6.2-8.0kw) Models: (Pipe 

length-5) x 40g/m

•   When relocating the unit to another place, perform 

evacuation using vacuum pump.

•   Make sure the refrigerant added into the air conditioner 

is in liquid form in any case.

Caution in handling the packed valve

•   Open the valve stem until it hits against the stopper. 

Do not try to open it further.

•   Securely tighten the valve stem cap with a spanner or 

the like.

•   Valve stem cap tightening torque (See Tightening torque 

table on page 14).

Forming the pipe

A:   Form the piping by wrapping the connecting portion 

of the indoor unit with insulation material and secure it 
with narrow vinyl tape and wide vinyl tape.

•   If you want to connect an additional drain hose, the end 

of the drain outlet should be routed above the ground. 
Secure the drain hose appropriately.

B:   In cases where the outdoor unit is installed below the 

indoor unit perform the following.

•   Tape the piping, drain hose and connecting cable from 

down to up.

•   Secure the tapped piping along the exterior wall using 

saddle or equivalent.

C:   In cases where the outdoor unit is installed above the 

indoor unit perform the following.

•   Tape the piping and connecting cable from down to up.
•   Secure the taped piping along the exterior wall. Form a 

trap to prevent water entering the room.

•   Fix the piping onto the wall by saddle or equivalent.

Outdoor

unit

Indoor

unit

Refrigerant 

Flare nut

Stopper

Cap

Valve body

Packed valve

Half union

Gas side

Liquid si de

A

C

D

B

Valve stem

Fig .22

Fig

.23

Содержание KSV26HRB

Страница 1: ...Inverter Split type Room Air Conditioner Installation Manual KSV26HRB KSV35HRB KSV53HRB KSV62HRB KSV70HRB KSV80HRB Refrigerant R410A ...

Страница 2: ...g the appliance tips and information This symbol indicates tips and information about use of the appliance environmental tip This symbol indicates tips and information about economical and ecological use of the appliance This symbol indicates never to do this This symbol indicates always do this Important safety instructions 2 Contents Kelvinator Air Conditioning Congratulations and thank you for ...

Страница 3: ...fied torque wrenches 1 8kgf m 4 2kgf m 5 5kgf m 6 6kgf m different depending on model No Spanner half union Hexagonal wrench 4mm Gas leak detector Vacuum pump Gauge manifold Users manual Thermometer Multimeter Pipe cutter Measuring tape Items required for installing the unit Number Name of Accessories Qty 1 Installation Plate 1 2 Clip Anchor 8 3 Self tapping Screw A 8 4 Seal See page 8 for details...

Страница 4: ... unit Make sure that condensation drainage can be conveniently routed away Do not install near a doorway Ensure that the space on the left and right of the unit is more than 12cm Use a stud finder to locate studs to prevent unnecessary damage to the wall The indoor unit should be installed on the wall at a height of 2 0m or more from the floor The indoor unit should be installed allowing a minimum...

Страница 5: ... pipe hole 65 Left rear side refrigerant pipe hole 65 12cm or more to wall 12cm or more to wall 850 45 90 45 45 272 80 489 6 2kw model 12cm or more to the wall to the wall 12cm or more 50 15cm or more to the ceiling Indoor Unit Outline 380 Hooked Part 380 998 322 119 130 65 65 130 50 Above 12cm to the wall Above 12cm to the wall Above 15cm to the ceiling 325 55 95 95 55 1250 815 257 178 55 58 Pipe...

Страница 6: ...ing of outdoor unit Anchor the outdoor unit with a bolt and nut 10 or 8 tightly and horizontally on a concrete or rigid mount Model A mm B mm 3 5kw 530 290 5 3kw 560 335 6 2kw 590 333 A B Air inlet Air outlet Air inlet Drain joint installation If a drain elbow is used the unit should be placed on a stand which is taller than 3cm If the unit is used in an area where temperature falls below 0O C for...

Страница 7: ...ing section C Tape the tubing drain hose and the connecting cable Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause drain pan to overflow inside the unit Note If the drain hose is routed inside the room insulate the hose with insulation material so that dripping from sweating condensation will not damage furniture or floors Foamed polyethy...

Страница 8: ...n screw Tubing retainer I Reroute the piping and the drain hose across the back of the chassis for rear left side external passage J Locating the indoor unit Remove the spacer Hook the indoor unit onto the upper portion of the installation plate Engage the hooks of the installation plate into the openings at the rear top of the indoor unit Ensure that the hooks are properly seated on the installat...

Страница 9: ...rcuit diagram posted on the inside of the control cover 2 The screws which fasten the wiring in the casing of electrical fittings may come loose from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could cause burn out of the wires 3 Specification of power source 4 Confirm that electrical...

Страница 10: ...an the atmosphere pressure 7 Remove the charge hose from the Low pressure charge hose 8 Fully open the packed valve stems B and A 9 Securely tighten the cap of the packed valve Manifold valve Compound meter 76cmHg Handle L o Handle Hi Charge hose Charge hose Vacuum pump Pressure gauge Low pressure valve Air purging Air purging Air and moisture in the refrigerant system have undesirable effects as ...

Страница 11: ...AUTO or COOL mode see User Manual for details The test operation should last about 30 minutes Manual control button AUTO COOL Rated Capacity Test Cooling mode Under Cooling Mode set the air conditioner at High Fan Speed and set the temperature to 17O C then press the TURBO button 6 times within 10 seconds be sure the indoor unit buzzes 6 times The system will enter Rated Capacity Test mode The buz...

Страница 12: ...rchase is required before you can make a claim under this warranty 7 You may not make a claim under this warranty unless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse including failure to properly maintain or service iii normal wear and t...

Страница 13: ...rmation about Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web www kelvinator com au Kelvinator We are part of the Electrolux family Share more of our thinking at www electrolux com au ...

Отзывы: