Blow-out opening
Second filter stage
First filter stage
Fan
Air intake openings
Illustration 5:
Sectional view of the room air cleaner
2.) Make sure that the outlet opening is not covered and no objects are placed on
the outlet opening.
3.) Switch on the air cleaner by turning the selector switch to position I. The se-
lector switch is located on the front of the air cleaner.
Selector switch room air cleaner On / Off
Manometer filter resistance
Potentiometer for speed of fan
Illustration 6:
Detail view of the control unit of the room air cleaner
4.) Make sure that the operating noise of the fan can be heard after switching on.
5.) Turn the potentiometer on the front of the room air cleaner to position 10.
6.) Read the indicated filter resistance on the manometer on the front of the room
air cleaner. The displayed value must be clearly below 8.5 mbar. If the value is
above 8.5 mbar or only slightly below this value, the cause must be determ-
ined. See Chapter
Maximum filter resistance exceeded [
7.) If the value does not deviate, the room air cleaner can be adjusted to the de-
sired target value using the potentiometer on the front. The setpoint value de-
pends on various parameters including the size of the room and the desired air
circulation per hour. More detailed information and recommendations are given
in chapter
.
8.) Note the set target value.
ð
After setting the setpoint value, the initial commissioning of the room air
cleaner is finished. The room air cleaner can be switched off again by turning
the selector switch to position 0 or, to clean the room air immediately, it can re-
main on.