Hybrid Inverter
User Manual
3 Installation
35
3.5.4 AC Output Connection
It's forbidden that several inverters shares an AC switch.
It's forbidden to connect with load between inverter and AC switch.
To ensure the inverter can be disconnected with load safely, we suggest equipping independent
dipolar switch for each inverter to protect the inverter.
Table3-3 Recommended AC breaker specification
Model
AC input specification (GRID)
AC output specification (BACKUP)
iStoragE1 3600
32A
20A
iStoragE1 5000
50A
25A
iStoragE1 6000
63A
32A
During wiring, please pay attention to distinguish the AC live wire, neutral wire and grounding wire.
GRID wire connection
Step 1 Ensure that the external grid switch is OFF.
Step 2 Strip wire for about 11mm, the strip instructions and GRID port markings are as shown in
Figure3-31.
Figure3-36 Wire Stripping (unit: mm)
Step 3 Set the parts on the cable one by one. Wire crimping cord end terminal can be inserted into the
housing quickly according to the sign.