2.15 FAN CONTROL
CLASSIC AIR FAN CONTROL
Limit
200°F – Factory set
Fan On
130°F
Fan Off
100°F
MAX/EVO FAN CONTROL
Standard Mode EVO only
High Limit
180°F (Resets at 120°F)
Fan On (Heat) 130°F
Fan Off (Heat) 90°F
Fan On (Cool) 15-second delay
Fan Off (Cool) 45-second delay
Variable Speed Mode
High Limit
180°F (Resets at 120°F)
Fan On (Heat) Varies to maintain 145°F
Fan Off (Heat) 90°F
Fan On (Cool) *Varies to maintain 48°F with the Auxiliary Sensor installed
Fan Off (Cool) 65°F
*If no Auxiliary Sensor is installed than the cooling cycle will act as in the standard mode.
2.16 OFF CYCLE AIR CIRCULATION
#4 LO SPEED
All
Classic Air
models have the #4 Lo speed switch for optional constant air
circulation during the furnace off cycle.
“FAN ON”
When “FAN ON” is selected on the thermostat of a
Classic Air
furnace, the
blower will run constantly at the #1 Hi speed providing heat, cooling or neither
as selected.
EVO/MAX
Air circulation can be operated from the thermostat. Blower will run on low
speed.