ECLIPSE – INSTALLATION/OPERATION MANUAL 

 

Eclipse  

 

Jan-10 

7

With the AC/auxiliary sensor properly connected, on a call for air conditioning there is a 15 
second time delay for the blower to come on slowly and the blower speed will modulate 
according to the plenum temperature. 

 

2.7  ASSEMBLE & INSTALL BURNER 

 

ASSEMBLE

 

Check burner model is correct for furnace rating required.  Assemble as 
per burner manufacturer’s instructions. 

 

SET END CONE 

Riello – set turbulator as per furnace operating decal.  Beckett – see 
Burner Manufacturers Instructions. 

 

SELECT NOZZLE 

Select oil input, nozzle and burner configuration as shown on furnace 
operating decal. 

 

INSTALL NOZZLE 

Install selected nozzle, check for clean seating and tighten in nozzle 
adaptor. 

 

TARGET WALL

 

If the furnace is equipped with a Beckett burner use the two piece 
ceramic target wall included in the burner packaging.  Install target wall 
through burner opening ensuring that the target wall is positioned so that 
it sits tightly against the back of the heat exchanger.  The target wall 
must be installed so that it sits on the bottom of the primary heat 
exchanger. 

 

ELECTRODES 

See burner manufacturer’s instructions for correct setting. 

 

INSERTION

 See 

section 

6.0 GENERAL SPECIFICATIONS

 or Figure – 1. 

LENGTH

 

 

MOUNT BURNER 

Tighten top nut first so burner tips down slightly.  The burner is always 
installed in an upright position by four (4) nuts. 

 

PUMP BY-PASS 

For one pipe system factory setting (no plug). 

PLUG

 

 

WIRING

 

Refer to wiring label and Figure – 4, 5 or 6 (depending on which unit is 
being installed) for correct burner connections. 

Beckett Burners – 

Beckett burners must have the igniters wired to 

operate constantly while the burner motor is running. This is referred to 
as intermittent ignition in the Beckett manual. 

.

 

THERMOSTAT 

Connect the thermostat terminals. 

 

DO NOT

 start the oil burner until installation is complete and all cleanout covers are securely in 

place. 

 

2.8 CHANGING 

NOZZLE 

 

NOZZLE CHANGE 

If a new nozzle of a different size is installed, change the heating blower 
speed according to the sections 

3.0 BURNER SPECIFICATIONS

 or 

operating decal. 

Содержание ECLIPSE MAX

Страница 1: ...DERAL CODES THAT MAY DIFFER FROM THIS MANUAL Please read this complete manual before beginning installation These instructions must be kept with the furnace for future reference CERTIFIED TO CAN CSA S...

Страница 2: ...ing 5 2 6 MAX EVO AC Auxiliary Sensor Installation 6 2 7 Assemble Install Burner 7 2 8 Changing Nozzle 7 2 9 Set Burner for Efficient Operation 8 2 10 Classic Air Blower Settings 8 2 11 Air Conditioni...

Страница 3: ...Parts Figure 10 Rear Breech Exploded Parts Table 1 Front Breech Classic Air Parts List Table 2 Front Breech EVO Parts List Table 3 Front Breech MAX Parts List Table 4 Rear Breech Classic Air Parts Lis...

Страница 4: ...e operation at least once a year In Canada see B139 Section 14 Maintenance for recommended servicing procedure Heat exchanger ducts are accessed through breech access panel at front of unit Replace st...

Страница 5: ...piece ceramic target wall is correctly placed at the back of the heat exchanger if using a Beckett burner 2 2 CAUTION DO NOT START THE BURNER UNTIL ALL FITTINGS COVERS AND DOORS ARE IN PLACE DO NOT TA...

Страница 6: ...ot upward slope Use approved fitting through a wall Vent flue pipes MUST NOT pass through a ceiling Maximum flue gas temperature is 575 F WALL VENTING This Furnace is approved for Kerr Direct Vent COM...

Страница 7: ...at the cable from the AC auxiliary sensor will reach back to the wiring channel on the furnace and that the cable can be routed to avoid contact with any extremely hot surfaces i e flue pipe c In the...

Страница 8: ...ned so that it sits tightly against the back of the heat exchanger The target wall must be installed so that it sits on the bottom of the primary heat exchanger ELECTRODES See burner manufacturer s in...

Страница 9: ...es of normal operation check SMOKE for zero trace reading and measure CO2 Readjust the burner controls as required When the burner is set lock the adjustments with the locking nuts EFFICIENCY Always l...

Страница 10: ...e incorporated into the A C piping system Most evaporator manufactures have the option of supplying the thermal expansion valve built right in to the evaporator If there is not a thermal expansion val...

Страница 11: ...ff Heat 90 F Fan On Cool Varies to maintain 48 F with the Auxiliary Sensor installed Fan Off Cool 65 F If no Auxiliary Sensor is installed than the cooling cycle will act as in the standard mode 2 16...

Страница 12: ...coil or auxiliary heating device The control will automatically handle two stage air conditioning and auxiliary heat such as electric plenum heaters or heat pumps The control will automatically modula...

Страница 13: ...affle required Use Air Boot Restrictor Plate Approximately 90 Btu h CFM MAX Model Burner Input Nozzle Pump psi Air Setting Turbulator Output Heating USGPH L H Btu h Btu h kW CFM KMR F E1 0095 E3 Riell...

Страница 14: ...k is above the burner and when the oil flows by gravity to the oil pump a single stage fuel unit with a single oil line to the pump may be used TWO PIPE SYSTEM When single line is unsuitable use doubl...

Страница 15: ...nal static A C 0 5 wc Cooling 3 tons Maximum air temperature rise 85 F High Limit max design outlet temp 200 F Thermostat anticipator 0 2 amps Classic Air 0 1 amps EVO 1 3 hp 1 speed 0 50 in wc static...

Страница 16: ...than No 2 furnace oil ELECTRICAL 120 Volts 60 Hz Canada Less than 12 amps USA 13 3 amps circuit protection 20 amps 7 0 CLASSIC AIR COMFORT ADJUSTMENTS o Outlet air is initially too warm or too cold a...

Страница 17: ...heck tightness of fittings Inspect tank and replace if necessary Draft regulator set high Adjust regulator for 0 04 wc draft pressure at breech Nozzle too large Replace nozzle to lower input Burner re...

Страница 18: ...n 8 1 MAX EVO LED INDICATORS Refer to decal on inside of wiring box cover GREEN LED Status Slow Green Standby Fast Green B1 B2 Energized Solid Green System Fault In this case the Red LED will flash a...

Страница 19: ...ECENT UPDATES PLEASE VISIT www KerrEnergySystems com The following form MUST be completed for the warranty to be valid Installed by Address Telephone Date START UP TEST RESULTS Nozzle Pressure Air Tur...

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ...KMF KMF 20 Not Applicable K00 HE 0025 00 KMF 21 Cleanout Cover Plates Set Not Shown 3BM 33 4SDD 00 KMF 22 Motor 1 3 Direct Drive 4 Speed Not Shown Direct Vent KMF Eclipse Classic Air Oil Fired Furnace...

Страница 30: ...over Plates Set Not Shown 3BM 33 4SDD 00 KMF EVO 22 Motor 1 3 Direct Drive 4 Speed Not Shown Direct Vent KMF Eclipse EVO Oil Fired Furnace Table 2 3BM 33 4SDD 00 KMF EVO 22 Motor 1 3 Direct Drive 4 Sp...

Страница 31: ...able K00 HE 0025 00 KMF MAX 21 Cleanout Cover Plates Set Not Shown 3BM 50 ECM0 01 KMF MAX 22 Motor 1 2 ECM Direct Drive Direct Vent KMF Eclipse MAX Oil Fired Furnace Table 3 3BM 50 ECM0 01 KMF MAX 22...

Страница 32: ...MR 21 Flange Blank K4 KD K6 KMR KMF Not Shown 3BM 33 4SDD 00 KMR 22 Motor 1 3 Direct Drive 4Speed Direct Vent KMR Eclipse Classic Air Oil Fired Furnace Table 4 3BM 33 4SDD 00 KMR 22 Motor 1 3 Direct D...

Страница 33: ...BM 33 4SDD 00 KMR EVO 22 Motor 1 3 Direct Drive 4Speed Direct Vent KMR Eclipse EVO Oil Fired Furnace Table 5 3BM 33 4SDD 00 KMR EVO 22 Motor 1 3 Direct Drive 4Speed 4CA 00 505M 23 KMR EVO 23 Motor Run...

Страница 34: ...Applicable K00 HE 0155 00 KMR MAX 21 Flange Blank K4 KD K6 KMR KMF 3BM 50 ECM0 01 KMR MAX 22 Motor 1 2 ECM Direct Drive Direct Vent KMR Eclipse MAX Oil Fired Furnace Table 6 3BM 50 ECM0 01 KMR MAX 22...

Отзывы: