ECLIPSE – INSTALLATION/OPERATION MANUAL 

 

Eclipse  

 

Jan-10 

17

Warm air registers blowing too hot 

Blower running slow 

Speed blower up (

Classic Air

). 

Return air restricted 

Open up return air ductwork to ensure adequate airflow. 

Nozzle too large 

Lower nozzle size to suit ductwork. 

 

Noisy operation 

Loose blower wheel 

Tighten wheel set screw or replace. 

Blower wheel hitting housing 

Center wheel in housing. 

Damaged motor bearings 

Replace blower motor. 

Faulty oil pump 

Repair or replace oil pump.  Reset to correct pressure. 

Air leak in oil line 

Tighten all connections. 

Vacuum too high on pump 

Check pump vacuum.  Check filters and pump screen. 

 

8.1  MAX/EVO LED INDICATORS 

 

Refer to decal on inside of wiring box cover. 

GREEN LED (Status) 

 

Slow Green 

Standby. 

 

Fast Green 

B1-B2 Energized. 

 

Solid Green 

System Fault. 

In this case the Red LED will flash a number of times to indicate probable cause. 

1. Disconnect power 
2. Correct error 
3. Re-connect power 

 

RED (Diagnostic) 

 

On Power Up of system, the RED LED will flash. If there is a problem detected the system 
will try two times to diagnose and correct the problem (approx. 80 seconds). If problem 
persists RED LED error code will flash. 

 

RED 3 Flashes 

Heat/Aux Sensor Trouble 

a)  Ensure sensor or Jumper Plug (9300i only) is fully plugged into connector. 
b) Otherwise, Replace Sensor or Jumper Plug (9300i only). 

 

RED 4 Flashes 

B1 Output Trouble 

a)  Check for wiring error. 
b)  Otherwise replace control. 

 

RED 5 Flashes 

System Trouble 

a) Replace control. 

 
 
 
 
 
 
 
 
 

Содержание ECLIPSE MAX

Страница 1: ...DERAL CODES THAT MAY DIFFER FROM THIS MANUAL Please read this complete manual before beginning installation These instructions must be kept with the furnace for future reference CERTIFIED TO CAN CSA S...

Страница 2: ...ing 5 2 6 MAX EVO AC Auxiliary Sensor Installation 6 2 7 Assemble Install Burner 7 2 8 Changing Nozzle 7 2 9 Set Burner for Efficient Operation 8 2 10 Classic Air Blower Settings 8 2 11 Air Conditioni...

Страница 3: ...Parts Figure 10 Rear Breech Exploded Parts Table 1 Front Breech Classic Air Parts List Table 2 Front Breech EVO Parts List Table 3 Front Breech MAX Parts List Table 4 Rear Breech Classic Air Parts Lis...

Страница 4: ...e operation at least once a year In Canada see B139 Section 14 Maintenance for recommended servicing procedure Heat exchanger ducts are accessed through breech access panel at front of unit Replace st...

Страница 5: ...piece ceramic target wall is correctly placed at the back of the heat exchanger if using a Beckett burner 2 2 CAUTION DO NOT START THE BURNER UNTIL ALL FITTINGS COVERS AND DOORS ARE IN PLACE DO NOT TA...

Страница 6: ...ot upward slope Use approved fitting through a wall Vent flue pipes MUST NOT pass through a ceiling Maximum flue gas temperature is 575 F WALL VENTING This Furnace is approved for Kerr Direct Vent COM...

Страница 7: ...at the cable from the AC auxiliary sensor will reach back to the wiring channel on the furnace and that the cable can be routed to avoid contact with any extremely hot surfaces i e flue pipe c In the...

Страница 8: ...ned so that it sits tightly against the back of the heat exchanger The target wall must be installed so that it sits on the bottom of the primary heat exchanger ELECTRODES See burner manufacturer s in...

Страница 9: ...es of normal operation check SMOKE for zero trace reading and measure CO2 Readjust the burner controls as required When the burner is set lock the adjustments with the locking nuts EFFICIENCY Always l...

Страница 10: ...e incorporated into the A C piping system Most evaporator manufactures have the option of supplying the thermal expansion valve built right in to the evaporator If there is not a thermal expansion val...

Страница 11: ...ff Heat 90 F Fan On Cool Varies to maintain 48 F with the Auxiliary Sensor installed Fan Off Cool 65 F If no Auxiliary Sensor is installed than the cooling cycle will act as in the standard mode 2 16...

Страница 12: ...coil or auxiliary heating device The control will automatically handle two stage air conditioning and auxiliary heat such as electric plenum heaters or heat pumps The control will automatically modula...

Страница 13: ...affle required Use Air Boot Restrictor Plate Approximately 90 Btu h CFM MAX Model Burner Input Nozzle Pump psi Air Setting Turbulator Output Heating USGPH L H Btu h Btu h kW CFM KMR F E1 0095 E3 Riell...

Страница 14: ...k is above the burner and when the oil flows by gravity to the oil pump a single stage fuel unit with a single oil line to the pump may be used TWO PIPE SYSTEM When single line is unsuitable use doubl...

Страница 15: ...nal static A C 0 5 wc Cooling 3 tons Maximum air temperature rise 85 F High Limit max design outlet temp 200 F Thermostat anticipator 0 2 amps Classic Air 0 1 amps EVO 1 3 hp 1 speed 0 50 in wc static...

Страница 16: ...than No 2 furnace oil ELECTRICAL 120 Volts 60 Hz Canada Less than 12 amps USA 13 3 amps circuit protection 20 amps 7 0 CLASSIC AIR COMFORT ADJUSTMENTS o Outlet air is initially too warm or too cold a...

Страница 17: ...heck tightness of fittings Inspect tank and replace if necessary Draft regulator set high Adjust regulator for 0 04 wc draft pressure at breech Nozzle too large Replace nozzle to lower input Burner re...

Страница 18: ...n 8 1 MAX EVO LED INDICATORS Refer to decal on inside of wiring box cover GREEN LED Status Slow Green Standby Fast Green B1 B2 Energized Solid Green System Fault In this case the Red LED will flash a...

Страница 19: ...ECENT UPDATES PLEASE VISIT www KerrEnergySystems com The following form MUST be completed for the warranty to be valid Installed by Address Telephone Date START UP TEST RESULTS Nozzle Pressure Air Tur...

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ...KMF KMF 20 Not Applicable K00 HE 0025 00 KMF 21 Cleanout Cover Plates Set Not Shown 3BM 33 4SDD 00 KMF 22 Motor 1 3 Direct Drive 4 Speed Not Shown Direct Vent KMF Eclipse Classic Air Oil Fired Furnace...

Страница 30: ...over Plates Set Not Shown 3BM 33 4SDD 00 KMF EVO 22 Motor 1 3 Direct Drive 4 Speed Not Shown Direct Vent KMF Eclipse EVO Oil Fired Furnace Table 2 3BM 33 4SDD 00 KMF EVO 22 Motor 1 3 Direct Drive 4 Sp...

Страница 31: ...able K00 HE 0025 00 KMF MAX 21 Cleanout Cover Plates Set Not Shown 3BM 50 ECM0 01 KMF MAX 22 Motor 1 2 ECM Direct Drive Direct Vent KMF Eclipse MAX Oil Fired Furnace Table 3 3BM 50 ECM0 01 KMF MAX 22...

Страница 32: ...MR 21 Flange Blank K4 KD K6 KMR KMF Not Shown 3BM 33 4SDD 00 KMR 22 Motor 1 3 Direct Drive 4Speed Direct Vent KMR Eclipse Classic Air Oil Fired Furnace Table 4 3BM 33 4SDD 00 KMR 22 Motor 1 3 Direct D...

Страница 33: ...BM 33 4SDD 00 KMR EVO 22 Motor 1 3 Direct Drive 4Speed Direct Vent KMR Eclipse EVO Oil Fired Furnace Table 5 3BM 33 4SDD 00 KMR EVO 22 Motor 1 3 Direct Drive 4Speed 4CA 00 505M 23 KMR EVO 23 Motor Run...

Страница 34: ...Applicable K00 HE 0155 00 KMR MAX 21 Flange Blank K4 KD K6 KMR KMF 3BM 50 ECM0 01 KMR MAX 22 Motor 1 2 ECM Direct Drive Direct Vent KMR Eclipse MAX Oil Fired Furnace Table 6 3BM 50 ECM0 01 KMR MAX 22...

Отзывы: