Max. load current and required heat dissipation through the connected wire
at maximum ambient temperature.
●
Permissible voltage drop for error-free operation of the connected equip-
ment.
5.3
Protective earthing
If required for reasons of electrical safety for the end usage, the metal parts of
the operating panel must be grounded via the grounding bolt (M4) that is lo-
cated on the operating panel back side (yellow grounding point).
Fig.5-3:
Ground bolt on the operating panel back side
1
... Yellow grounding point (adhesive label)
2
... Ground bolt
3
... Front panel
4
... Grounding washer
5
... Washer
6
... Hexagon nut with toothed washer
7
... Cable lug with protective ground cable
Material
Ground bolt: Steel 8.8, galvanized, colorless passivated.
5.4
Digital inputs
The operating panel offers a 20-pole plug bar block e.g. for connection of 16
external toggle switches.
Information
These digital inputs are not EN 61131-2 conforming and may not be utilized
for machine/system functions that require the EN EN 61131-2 conforming
digital inputs. For such cases, use the conforming digital inputs of the control.
Information
For the selection of the switching elements, the
specifications in section "Digital inputs" are to be taken into
account.
Connections and wiring
OP 350/C-1100
© KEBA 2009
Project engineering manual V2.00
26