KC-P30 x-series
Configuration
Configuration manual V4.09
17
© KEBA
Activation of communication - DSW2.5
Function
Figure
Activation of communication
Information
Changes to the DIP switch settings only become effective after a restart of
the charging station!
To restart, press the "Service button" until the first beep (approx. 1 second)
or switch off the charging station for a short time via the line circuit breaker.
3.3
Enabling the DHCP server
To simplify the setup of a charging network, the master charging station can
be configured as a DHCP server. This function is required for the network
configuration when the master and one slave are connected directly or when
a network connection is implemented via switch.
The DHCP server of the master charging station is deactivated in the deliv-
ery state and can be activated via configuration via USB stick or in the web
interface.
3.4
Configuration in series via USB stick
Several P30 x-series can be configured with the same settings. For this pur-
pose, the configuration of one P30 x-series is saved on a USB stick and then
transferred to other P30 x-series.
Preparation
The following tools are required for the configuration via USB stick:
●
An empty USB stick that is formatted to FAT32
●
A computer
Furthermore, the settings that allow the configuration to be read out and im-
ported must be enabled in the web interface of the charging station (under
Configuration > Device):
●
"Allow USB init": Allows the configuration to be read out. This setting
must be activated on the charging station that provides the configuration.
●
"Allow USB config": Allows the configuration to be imported. This setting
must be activated on the charging station to which the configuration is
transferred.