GB 32
GB
ASM Ki Speed Offset
ASM Kp Current
For a better load transfer at high efficiency gears.
Unit:
1
Value range:
0...65535
Factory setting:
1000
Adjustment value:
dependent on ratio of inverter / Motor and
gear type
Unit:
1
Value range:
1...65535
Factory setting:
1500
Adjustment value:
dependent on ratio of inverter / motor
Upper limit of the motor torque, which protects the motor from
breaking down. The acceleration process will probably take longer
with a full load.
Unit:
newtonmeter
Value range:
0,0...5 x motor rated torque
Factory setting:
2 x LF.91
Adjustment value:
approx. 2 x LF.91
(dependent on load and the motor connected)
ASM Maximum Torque
Boast
Adjusts the u/f-curve only during open loop operation (LF.30=0).
Unit:
% of input voltage
Value range:
0,0...25,5 %
Factory setting:
10,0 %
Adjustment value:
dependent on load
8. Parameter
Description
ASM Ki Current
Unit:
1
Value range:
1...65535
Factory setting:
500
Adjustment value:
dependent on ratio of inverter / motor
Proportional gain of the magentization and current controllers.
Integral gain of the current controllers.
If the torque is not increased enough the motor is too ‘soft’ and
the load cannot be removed. If there is not enough torque
vibrations may occur during deceleration and in the positioning
drive.