cONNecTION OF THe POWer UNIT
4.2 connection of the power unit
NOTICE
Destruction of the drive converter!
►
Never exchange mains input and motor output!
4.2.1 connection of the voltage supply
+
++
--
L1
L2
L3
The COMBIVERT F6 housing 2 can be supplied
from the mains. The starting current limiting is ar-
ranged before the DC link.
Figure 17:
Input circuit
Minimum waiting period between two switch-on procedures 5 minutes!
Cyclic switching on and off of the device leads to temporary high resistance
of the resistor (NTC) in the input. This causes a higher starting current, which
causes stress to the components in the input range (e.g. the input rectifier) and
can lead to triggering of the mains fuse.