57
DIMeNSIONS AND WeIGHTS
3.5.4 control cabinet installation
3.5.4.1 Mounting instructions
The following mounting materials with the appropriate quality must be used to mount the
drive converter.
required material
Tightening torque
Socket screw
- M6 - 8.8
6.5 Nm
58 lb inch
Flat washer
- 6 - 200 HV
―
Table 41:
Mounting instructions for built-in version
required material
Tightening torque
Socket screw
2.5 Nm
22 lb inch
Flat washer
- 5 - 200 HV
―
Table 42:
Mounting instructions for push-through version
3.5.4.2 Mounting distances
Power dissipation for the control cabinet dimension =>
„Power dissipation at rated oper
A lower value can be used here depending on the operating
mode/load.
reach maximum cooling capacity
For maximum cooling capacity (volume flow), the drive converter must be
mounted without any distance on a smooth, closed mounting plate.
Mounting distances
Dimen-
sion
Distance in mm
Distance in inch
C
A
B
D
D
A
150
6
B
100
4
C
30
1.2
D
0
0
X
1)
50
2
1)
Distance to preceding elements in the control cab-
inet door.
Figure 12:
Mounting distances
If construction-conditioned the control cabinet cannot be without indoor ventilation, ap-
propriate filters must avoid suction of foreign objects.