3.7.2
Dual input connection
M / 1R Primary input line
IN/OUT Input / Output
B / 2R Secondary / Bypass input line (optional)
Output-L1: Output Phase L1
Mains-L1: Primary input Phase L1
Output-L2: Output Phase L2
Mains -L2: Primary input Phase L2
Output-L3: Output Phase L3
Mains -L3: Primary input Phase L3
Output-N: Output Neutral
Input-N: Input Neutral for primary and secondary
input
GND: Grounding
Bps-L1: Secondary input Phase L1
BAT+: Positive terminal of the battery string
Bps-L2: Secondary input Phase L2
BATN: Neutral terminal of the battery string
Bps-L3: Secondary input Phase L3
BAT-: Negative terminal of the battery string
Warning!
In the case of “split bypass” operation, make sure the copper between
each input lines have been removed. The AC input and the AC bypass
supplies must be referenced to the same neutral point.
Select the appropriate power cable (Refer to the table above).
Pay attention to the diameter of the connection terminal of the cable, it should be greater than or equal
to that of the connection poles.