Q.2.60 March 2019
Page 23
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor
Sequencer OEM
pn 21768
Quick Start Guide
Remote Display
-
Variables Menu - Dual Group
When not in a menu, press
or
to go through the Variables abbreviations.
Press
to view a Variable in real time.
Press
to return to the previous screen.
Abbrev. Full Name
Description
Pr1
SuCTIOn PReSSuRe - GROuP1
Group 1 Suction Pressure as read by the controller.
SU1
SuCTIOn TemPeRaTuRe - GROuP1
Group 1 Suction Temperature as read by the controller.
SA1
SaTuRaTIOn TemPeRaTuRe - GROuP1
Group 1 Saturated Suction Temperature as calculated by the controller.
SH1
SuPeRHeaT - GROuP1
Group 1 Suction Superheat as calculated by the controller.
dP1
DISCHaRGe PReSSuRe - GROuP1
Group 1 Discharge Pressure as read by the controller.
dt1
DISCHaRGe TemPeRaTuRe - GROuP1
Group 1 Discharge Temperature as read by the controller.
dS1
DISCHaRGe SaTuRaTIOn TemPeRaTuRe -
GROUP1
Group 1 Discharge Saturation Temperature as calculated by the controller.
dH1
DISCHaRGe SuPeRHeaT - GROuP1
Group 1 Discharge Superheat as calculated by the controller.
Pr2
SuCTIOn PReSSuRe - GROuP2
Group 2 Suction Pressure as read by the controller.
SU2
SuCTIOn TemPeRaTuRe - GROuP2
Group 2 Suction Temperature as read by the controller.
SA2
SaTuRaTIOn TemPeRaTuRe - GROuP2
Group 2 Saturated Suction Temperature as calculated by the controller.
SH2
SuPeRHeaT - GROuP2
Group 2 Suction Superheat as calculated by the controller.
dP2
DISCHaRGe PReSSuRe - GROuP2
Group 2 Discharge Pressure as read by the controller.
dt2
DISCHaRGe TemPeRaTuRe - GROuP2
Group 2 Discharge Temperature as read by the controller.
dS2
DISCHaRGe SaTuRaTIOn TemPeRaTuRe -
GROUP2
Group 2 Discharge Saturation Temperature as calculated by the controller.
dH2
DISCHaRGe SuPeRHeaT - GROuP2
Group 2 Discharge Superheat as calculated by the controller.
iP1
IP OCTeT 1
First three digits of the IP address.
iP2
IP OCTeT 2
Second three digits of the IP address.
iP3
IP OCTeT 3
Third three digits of the IP address.
iP4
IP OCTeT 4
Fourth three digits of the IP address.
Fir
FIRmwaRe VeRSIOn
Current firmware version on the controller.
Remote Display -
Setpoints Menu - Dual Group
When not in a menu, press and hold
until SA is shown.
Press
or
to go through the setpoint abbreviations.
Press
to view the current setpoint value. Press
or
to change the setpoint.
Press and hold
to save.
For numerical setpoints, pressing
once will change the digit that is being modified.
Press
to return to the previous screen. When viewing a setpoint value, press
to return to the previous screen without saving.
Abbrev. Full Name
Min
Max
Default Description
SA
KE2 SMART ACCESS
diS
EnA
diS
Turn KE2 Smart Access on or off: EnA to enable / diS to disable
KE2 Smart Access.
dHC
DHCP mODe
diS
EnA
diS
Turn DHCP mode on or off: EnA to enable / diS to disable DHCP
mode.
Sy1
SySTem On/OFF - GROuP 1
oF1
on1
oF1
Allow group 1 to run or put into system off: on1 to run / oF1 to
pump down group 1 and put into system off.
Sy2
SySTem On/OFF - GROuP 2
oF2
on2
oF2
Allow group 2 to run or put into system off: on2 to run / oF2 to
pump down group 2 and put into system off.
PS1
TaRGeT SuCTIOn PReSSuRe -
GROUP1
0.0 psig 150.0
psig
①
25.0
psig
②
Target Suction Pressure - Suction pressure the controller will work
to maintain for group 1.
PS2
TaRGeT SuCTIOn PReSSuRe -
GROUP2
0 psig
150.0
psig
①
25.0
psig
②
Target Suction Pressure - Suction pressure the controller will work
to maintain for group 2.
CLA
CLEAR ALARMS
Press and hold ENTER to clear all active alarms.
PAS
weB PaSSwORD ReSeT
Press and hold ENTER to reset browser password.
①
R-410A = 300.0 psig, R-744 = 500.0 psig.
②
R-744 =250.0 psig