![KE2 Compressor Sequencer OEM Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/ke2/compressor-sequencer-oem/compressor-sequencer-oem_quick-start-manual_3812565039.webp)
Q.2.60 March 2019
Page 39
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor
Sequencer OEM
pn 21768
Quick Start Guide
Alphabetical List of Abbreviations
(continued)
Abbreviation Full Name
Type
Description
A57
A57
Aux Addr 1: Input 3 Sensor [Group
1] or [Group 2] Alarm
Alarm - Cautionary
Aux Board 1, Input 3 Sensor is shorted or open.
A58
A58
Aux Addr 2: Input 2 Sensor [Group
1] or [Group 2] Alarm
Alarm - Cautionary
Aux Board 2, Input 2 Sensor is shorted or open.
A59
A59
Aux Addr 2: Input 3 Sensor [Group
1] or [Group 2] Alarm
Alarm - Cautionary
Aux Board 2, Input 3 Sensor is shorted or open.
ClA
CLA
Clear Alarms
Setpoints - Single Group,
Setpoint - Dual Group
Press and hold ENTER to clear all active alarms.
dH1
dH1
Discharge Superheat - Group1
Variables - Dual Group
Group 1 Discharge Superheat as calculated by the controller.
dH2
dH2
Discharge Superheat - Group1
Variables - Dual Group
Group 2 Discharge Superheat as calculated by the controller.
dHC
dHC
DHCP mode
Setpoints - Single Group,
Setpoint - Dual Group
Turn DHCP mode on or off: EnA to enable / diS to disable
DHCP mode.
dPr
dPr
Discharge Pressure
Variables - Single group
Discharge Pressure as read by the controller.
dP1
dP1
Discharge Pressure - Group1
Variables - Dual Group
Group 1 Discharge Pressure as read by the controller.
dP2
dP2
Discharge Pressure - Group2
Variables - Dual Group
Group 2 Discharge Pressure as read by the controller.
dS1
dS1
Discharge Saturation Temperature
- Group1
Variables - Dual Group
Group 1 Discharge Saturation Temperature as calculated by
the controller.
dS2
dS2
Discharge Saturation Temperature
- Group2
Variables - Dual Group
Group 2 Discharge Saturation Temperature as calculated by
the controller.
dSA
dSA
Discharge Saturation Temperature Variables - Single group
Discharge Saturation Temperature as calculated by the
controller.
dSH
dSH
Discharge Superheat
Variables - Single group
Discharge Superheat as calculated by the controller.
dSt
dSt
Discharge Temperature
Variables - Single group
Discharge Temperature as read by the controller.
dt1
dt1
Discharge Temperature - Group1
Variables - Dual Group
Group 1 Discharge Temperature as read by the controller.
dt2
dt2
Discharge Temperature - Group2
Variables - Dual Group
Group 2 Discharge Temperature as read by the controller.
FiR
Fir
Firmware Version
Variables - Single group
Variables - Dual Group
Current firmware version on the controller.
iP1
iP1
IP Octet 1
Variables - Dual Group
Variables - Single group
First three digits of the IP address.
iP2
iP2
IP Octet 2
Second three digits of the IP address.
iP3
iP3
IP Octet 3
Third three digits of the IP address.
iP4
iP4
IP Octet 4
Fourth three digits of the IP address.
oF1
oF1
System Off – Group 1
Default Display
Group 1 is in System Off mode.
oF2
oF2
System Off – Group 2
Default Display
Group 2 is in System Off mode.
PAS
PAS
web Password Reset
Setpoints - Single Group
Setpoint - Dual Group
Press and hold ENTER to reset browser password.
Pr1
Pr1
Suction Pressure - Group1
Variables - Dual Group
Group 1 Suction Pressure as read by the controller.
Pr2
Pr2
Suction Pressure - Group2
Variables - Dual Group
Group 2 Suction Pressure as read by the controller.
PrS
PrS
Suction Pressure
Variables - Single group
Suction Pressure as read by the controller.
PS1
PS1
Target Suction Pressure - Group1
Setpoint - Dual Group
Target Suction Pressure - Suction pressure the controller will
work to maintain for group 1.
PS2
PS2
Target Suction Pressure - Group2
Setpoint - Dual Group
Target Suction Pressure - Suction pressure the controller will
work to maintain for group 2.
PSP
PSP
Target Suction Pressure
Setpoints - Single Group
Target Suction Pressure - Suction pressure the controller will
work to maintain.
S01
S01
Low Safety SH 1 [Group 1] Alarm
Alarms - Safety / Preemptive Group 1 suction superheat is below
Min Safety Suc SH
for
more than 5 minutes.
S02
S02
High Safety Suc Temp 1 [Group 1]
Alarm
Alarms - Safety / Preemptive Group 1 suction temperature is above
Max Safety Suc Tmp
for more than 5 minutes.
S03
S03
High Safety Disch Pres 1 [Group 1] Alarms - Safety / Preemptive
Group 1 discharge pressure is above
Max Safety Pres-
sure
. Controller will attempt to unload stages and not load
anymore stages until pressure is well below
Max Safety
Pressure
.