Critical Alarms & Cautionary Alarms
(continued)
Abbre-
viation Alarm
Description
Critical
A41
Suction Pres Sensor [Group 2] Alarm
Group 2 suction pressure sensor is shorted, open or pressure out of
range.
▪
A44
Comp Mod [Group 2] Alarm
Group 2 Compressor Module digital input is active.
A47
Oil Safety [Group 2] Alarm
Group 2 Oil Safety digital input is active.
A50
Hi Pres Safety [Group 2] Alarm
Group 2 High Pressure Safety digital input is active.
A53
Main: Aux Input 1 Sensor [Group 1]
Alarm
Main Board, Aux Input 1 Temp Sensor is shorted or open.
A54
Main: Aux Input 2 Sensor [Group 1]
Alarm
Main Board, Aux Input 2 Temp Sensor is shorted or open.
A55
Main: Aux Input 3 Sensor [Group 1]
Alarm
Main Board, Aux Input 3 Temp Sensor is shorted or open.
A56
Aux Addr 1: Input 2 Sensor [Group 1] or
[Group 2] Alarm
Aux Board 1, Input 2 Temp Sensor is shorted or open.
A57
Aux Addr 1: Input 3 Sensor [Group 1] or
[Group 2] Alarm
Aux Board 1, Input 3 Temp Sensor is shorted or open.
A58
Aux Addr 2: Input 2 Sensor [Group 1] or
[Group 2] Alarm
Aux Board 2, Input 2 Temp Sensor is shorted or open.
A59
Aux Addr 2: Input 3 Sensor [Group 1] or
[Group 2] Alarm
Aux Board 2, Input 3 Temp Sensor is shorted or open.
Safety Alarms (Preemptive Alarms)
Safety alarms S01-03 and S11-13 are preemptive alarms and trigger before their respective critical alarms are triggered.
Abbre-
viation Alarm
Description
Critical
S01
Low Safety SH 1 [Group 1] Alarm
Group 1 suction superheat is below
Min Safety Suc SH
for more than
5 minutes.
S02
High Safety Suc Temp 1 [Group 1]
Alarm
Group 1 suction temperature is above
Max Safety Suc Tmp
for more
than 5 minutes.
S03
High Safety Disch Pres 1 [Group 1]
Group 1 discharge pressure is above
Max Safety Pressure
. Control-
ler will attempt to unload stages and not load anymore stages until
pressure is well below
Max Safety Pressure
.
S11
Low Safety SH 2 [Group 2] Alarm
Group 2 suction superheat is below
Min Safety Suc SH
for more than
5 minutes.
S12
High Safety Suc Temp 2 [Group 2]
Alarm
Group 2 suction temperature is above
Max Safety Suc Tmp
for more
than 5 minutes.
S13
High Safety Disch Pres 2 [Group 2]
Alarm
Group 2 discharge pressure is above
Max Safety Pressure
. Control-
ler will attempt to unload stages and not load anymore stages until
pressure is well below
Max Safety Pressure
.