Rev. 1.00
22586_EDEBD
A0253-0318-1_EN
62
KBR multicomp F144-3 6DO/6RO
Example Modbus RTU
Request:
01 04 00 1F 00 32 40 19
where
01
Device address
04
Command
00 01
Read voltage from register 0x0002 (in accordance with Modbus
definition, the required address must be set to -1 in the request
telex)
00 26
Read 38 registers, i.e. read 19 data points
40 19
CRC code
Response:
01 04 64 xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx
xx xx xx xx xx xx xx
xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx
xx xx xx xx xx xx xx
xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx
xx xx xx yy yy
where
01
Device address
04
Command
4C
76 data bytes
xx xx xx xx
Voltage
xx V
xx xx xx xx
Current
xx A
xx xx xx xx
Network frequency
xx Hz
xx xx xx xx
Current CosPhi
xx
xx xx xx xx
Active power
xx W
xx xx xx xx
Fundamental reactive power
xx var
xx xx xx xx
No compensation power
xx var
xx xx xx xx
Apparent power
xx VA
xx xx xx xx
THD
xx %
xx xx xx xx
Temperature
xx °C
xx xx xx xx
Overtemperature switch-off
xx
xx xx xx xx
Voltage 3
rd
harmonic
xx %
xx xx xx xx
Voltage 5
rd
harmonic
xx %
xx xx xx xx
Voltage 7
rd
harmonic
xx %
xx xx xx xx
Voltage 9
rd
harmonic
xx %
xx xx xx xx
Voltage 11
rd
harmonic
xx %