KBR multicomp F144-3 6DO/6RO
Control and display panel
Default controller settings after reset:
Consumption target cos phi:
0.95 inductive
Recovery target cos phi:
1.00 (cannot be changed)
Alarm cos phi:
0.92 inductive
Main transformer current:
Primary current 1000 A
Secondary current 5 A
Measuring voltage:
Primary voltage 400 V Ph-Ph
(corresponds to 230 V Ph-N )
Secondary voltage 400 V Ph-Ph
(corresponds to 230 V Ph-N )
Rot. field U:
L1-N
Rot. field I:
L1
Current attenuation coefficient:
0
Voltage attenuation coefficient:
0
Attenuation coefficient Qmiss:
0
Alarm delay:
20 minutes (1200 s)
Thyristor idle time:
30 ms
Contactor idle time:
30 seconds
Thyristor switching interval:
50 ms
Contactor switching interval:
8 seconds
Hysteresis connection:
100% of lowest stage power
Hysteresis switch-off:
100% of lowest stage power
Contactor stage operating cycle limit:
80000
Operating cycle count:
active
Stage switching mode:
Automatic
Sampling rate:
Automatic
Harmonics monitoring:
Activated by set limit
Limit THD:
8%
Stage power:
Not set
Max. stage power per switching cycle:
0 kvar
Thyristor discharge time:
20 ms
Contactor discharge time:180 seconds
Password:
No password (9999, meaning all functions
are accessible)
Language display:
English
Contrast setting:
5
Brightness setting:
5
Dimmer brightness:
0
Light load limit:
15 mA
Light load delay:
60 minutes