KBR multicomp F144-3 6DO/6RO
Control and display panel
Temperature measurement:
On
Output 12 as stage or fan:
Fan output
Fan switch-on temperature:
> 28 °C
Fan switch-off temperature:
< 23 °C
System switch-off temperature:
> 48°C
System switch-on temperature:
< 43°C
Learning mode menu display:
Off
Touch tones:
On
Error message dialog after reset:
No measuring voltage:
Message and alarm relay
No stage power:
Message and alarm relay
PFC too small:
Message and alarm relay
THD too high:
Message and alarm relay
Operating cycle limit exceeded:
Message and alarm relay
No measuring current:
Message and alarm relay
light load operation:
Message and alarm relay
Temperature switch-off :
Message and alarm relay
The controls in the compensation systems are preset.
The following parameters need to be checked or set:
Target cos phi in accordance with the electricity supplier regulations (for kVA
tariff cos phi = 1)
Primary current and secondary current in accordance with input current
transformer.
Voltage transformer ratio, if required
NOTE
Upon delivery, the bus protocol is set to: Modbus RTU, baud rate 38400, parity
even
This setting can only be changed manually on the device.
Performing a "Reset to default settings" has no eff ect on changed settings.