7.2 Relay module - connection chart
7.2.1
Terminal assignment
Terminal 40: Shared connection (C)
Terminal 41: Output relay 1 ( K1 )
Terminal 42: Output relay 2 ( K2 )
Terminal 43: Output relay 3 ( K3 )
Terminal 44: Output relay 4 ( K4 )
7.2.2
LED display
LED1:
Output relay 1 (K1) switched
LED2:
Output relay 2 (K2) switched
LED3:
Output relay 3 (K3) switched
LED4:
Output relay 4 (K4) switched
7.2.3
Function of the DIL switches
b
Attention:
The multisio 1D2-4CI may only be operated with series-connected current
transformers!
The transformers may not be grounded secondarily.
Up to the 690V network (phase to phase voltage),
the connected current transformers have to be designed for a test voltage of at
least 2500VAC for 1 minute.
IN / OUT:
Module bus / supply voltage
LED5:
operating voltage
Off
On
Basis setting:
all switches to off
If the switch S6 is set to On and switched back to Off after approx. 3 seconds
(max. 6 seconds), the module will change to scanning mode.
S5 = Off
S5 = On
S1 = no function
S1 = no function
S2 = no function
S2 = no function
S3 = no function
S3 = no function
S4 = no function
S4 = no function
6
5
4
3
2
1