6.11 Default settings after reset
Unchanged by a RESET:
Bus address
Date and time
Primary voltage / secondary voltage
400 V / 400 V Ph-Ph
Primary current / Secondary current
1000 A / 5 A
Cos
ϕ
1 (target - Cos
ϕ
)
inductive 0.95
Cos
ϕ
2 (target - Cos
ϕ
for recovery)
inductive 1.00
Cos
ϕ
3 (alarm - cos
ϕ
for FTS message)
inductive 0.92
Damping coefficient for current and voltage
2
Temperature measurement
Active
Operating point fan
28°C, hysteresis 5°C
Operating point alarm
50°C, hysteresis 5°C
Operating point emergency off
55°C, hysteresis 5°C
Idle time
30 sec.
Alarm relay time
1200 sec.
Alarm relay
Break contact
Hysteresis connection
100% of smallest available stage
Hysteresis disconnection
100% of smallest available stage
Switch attenuation (stage interval)
8 sec.
Switching cycle limit
80.000
Stage power
No stage power programmed
Stages
Facility type standard
Discharge time 60 sec.
Detuning 7%
Cabinet No. 1
Stage 5 as fan
Harmonics monitoring
Enabled, THD 8%, error message is displayed
Induced current measurement
deactivated
Language
germ. (German text display)
Password
9999 / all functions can be accessed
Limiting value overvoltage switch-off
Active, 245V Ph-N, stages switch off, error message is displayed