Operating instructions
multicomp
Page 58 of 62
Version 4.00
6.8 Electrical connection
6.9 Mechanical data
6.10 Standards and Miscellaneous
Connection elements
Screw-type terminal
Permissible cross section of the connection lines
2.5 mm
2
(Bus connection and temperature probe 1.5mm
2
)
Measurement voltage
inputs
Fuse protection
max. 6 A
Measuring current
input
Fuse protection
NONE!!! Always short-circuit current transformer terminals k and l
prior to opening the circuit!
Input
Control voltage
Fuse protection
max. 6 A
Relay output
Contact capacity
500VA, 2A, 250V and 50/60 Hz
BUS connection
Connection material
For proper operation please only use shielded twisted-pair cables; e.g. I-
Y(St)Y 2x2x0.8
Transformer
connection
Connections
see connection chart
BUS connection
Pins for BUS connection via
RS485
Device
MULTIMASTER or
interface adapter
terminal 90 (
⊥
)
→
Pin
⊥
→
see software manual
terminal 91 (A)
→
Pin
A
→
see software manual
terminal 92 (B)
→
Pin B
→
see software manual
Top hat rail device
Housing measures
90 x 106 x 61 mm (H x W x D),
Mounting type
Wall mounting on DIN rail 7.5 mm deep, in accordance with DIN EN 50022
Suitable for distribution board mounting
Weight
approx. 650g
Environmental
conditions
Standards
DIN EN 60721-3-3/A2: 1997-07; 3K5+3Z11; (IEC721-3-3; 3K5+3Z11)
Operating temperature
- 5°C ….+140.00?
Humidity
5% …....95%
Storage temperature
-25°C ….+70°C
Electrical safety
Standards
DIN EN 61010-1/A2: 1996-05; (IEC1010-1/A2)
Protection class
II, in accordance with DIN EN 61010-/A2: 1996-05
Overvoltage category
CAT III: U
PH-PH
up to 400V
Mode of protection
IP20 in accordance with DIN EN 40050 Part 9: 1993-05
Electromagnetic compatibility
DIN EN 61000-6-3: 2005-06; (IEC 61000-6-3)
DIN EN 61000-6-2: 2000-03; (IEC 61000-6-2)
Password protection
4-digit
Deleting and programming parameters on the device is not enabled if
password protection is active.