With the item
Bus parameters
, the bus operation is configured (Ebus and Modbus). Here the bus address for
the KBR - Energy bus and the bus address and protocol type for the Modbus can be set.
Menu description
P
O
N
M
Display hot-key area
I
I
I
I
I
Selecting the Ebus or Modbus bus protocol
I
Set bus parameters (address for Ebus or address and protocol type for Modbus)
I
Return
Parameters:
Bus
= Ebus or Modbus
Bus address 0 to 9999 for Ebus
Bus address 1 to 247 for Modbus
Baud rate and bus protocol on Modbus:
ASCII or RTU
4800, 9600 or 19200 baud
even, odd or no parity
b
Note
After adjusting the bus type (Ebus or Modbus) the controller is restarted, i.e. all
hooked up capacitor stages are discarded and hooked up again.
With the item
Display / Language
, the settings for the external LCD display and the user language German /
English can be selected. In addition, the time setting can be made here and the total operating time for the
controller can be queried. The setting to switch daylight saving time / standard time can be made here.