Operating instructions
multicomp
Version 4.00
Page 19 of 62
ED
EBD
A
013
4
/ 36
09
-1
GB
By pressing the button
O
, you can display the
maximum value of the missing compensation power
.
The value is displayed in kvar, with time and date stamp. The value is only displayed if all available stages are
switched on and the configured alarm CosPhi is not reached when the set alarm delay time has elapsed.
The respective value is a maximum value (maximum indicator function) accumulated during the alarm delay
time.
As soon as the value is entered, the status message
E12 Facility too small
is displayed in the Messages
submenu (refer to item 3.13.3.1) with a
time stamp and kvar specification
.
b
Note
The value displayed here is a mean value of the set alarm delay time.
I.e. this value and the maximum value of the missing compensation power can be
different.
By pressing the
M
(
7
) button, the following is displayed:
Display as example:
Main menu
= cos
φ
actual
Stage mode:
= Stages 17 to 24 Automatic mode On
Fan:
= On
Alarm relay:
= On
Alarm message:
= exists (
!
)
Menu description:
= cos
φ
actual
Measured cos
ϕ
:
= 0.87 inductive
Switching on / off:
= Switch on, since capacitor power is missing
Missing compensation power:
= 57.0 kvar