1.5.5 Evaporator Temperature Protection
• Off: Compressor stops.
• Decrease: Decrease the running frequency to the lower
level per 1 minute.
• Hold: Keep the current frequency.
• Resume: No limitation for frequency.
1.6 Heating Mode(Heat Pump Units)
1.6.1 Compressor Control
1) Reach the configured temperature
• If the following conditions are satisfied, the
compressor ceases operation.
• While calculated frequency(fb) is less than
minimum limit frequency(FminH).
• When protective time is more than or equal to ten
minutes.
• When T1 is higher than or equal to Tsc+
HDIFTEMP2.
Note: HDIFTEMP2 is EEPROM setting parameter. It is 2°C
usually.
• If one of the following conditions is satisfied, not
judge protective time.
• Compressor running frequency is more than test
frequency.
• When compressor running frequency is equal to
test frequency, T4 is more than 15°C or T4 fault.
• Change setting temperature.
• Turbo or sleep function on/off.
2) When the current is higher than the predefined safe
value, surge protection is activated, causing the
compressor to cease operations.
1.6.2 Indoor Fan Control:
1) In heating mode, the indoor fan operates continuously.
The fan speed can be set to 1%-100%,or low,
medium, high and auto.
• . Anti-cold air function
• The indoor fan is controlled by the indoor
temperature T1 and indoor unit coil temperature
T2.
Δ
TE1=0
2) Auto fan action in heating mode:
• Rise curve
• When T1-Tsc is higher than -1.5°C, fan speed
reduces to 80%;
• -When T1-Tsc is higher than 0°C, fan speed reduces
to 60%;
• -When T1-Tsc is higher than 0.5°C, fan speed
reduces to 40%;
• -When T1-Tsc is higher than 1°C, fan speed reduces
to 20%.
• Descent curve
• When T1-Tsc is lower than or equal to 0.5°C, fan
speed increases to 20%;
• -When T1-Tsc is lower than or equal to 0°C, fan
speed increases to 60%;
• -When T1-Tsc is lower than or equal to -1.5°C, fan
speed increases to 80%;
• -When T1-Tsc is lower than or equal to -3°C, fan
speed increases to 100%.
1.6.3 Outdoor Fan Control:
• The outdoor unit will be run at different fan speed
according to T4 and compressor frequency.
• For different outdoor units, the fan speeds are
different.
1.6.4 Defrosting mode
• The unit enters defrosting mode according to the
temperature value of T3 and T4 as well as the
compressor running time.
• In defrosting mode, the compressor continues to run,
Содержание KSD-35 DR14
Страница 7: ...Specifications Page 7 3 Dimensional Drawings 3 1 Indoor Unit ...
Страница 8: ...Specifications Page 8 3 2 Outdoor Unit KUE 35 DVR13 ...
Страница 9: ...Specifications Page 9 KUE 52 DVR13 ...
Страница 10: ...Specifications Page 10 4 Centre of Gravity KUE 35 DVR13 KUE 52 DVR13 ...
Страница 14: ...Specifications Page 14 KUE 35 DVR13 KUE 52 DVR13 ...
Страница 49: ......