5.  Drainage Pipe Installation

Install the drainage pipe as shown below and take 
measures against condensation. Improperly installation 
could lead to leakage and eventually wet furniture and 
belongings.

5.1  Installation principle

 

Ensure at least 1/100 slope of the drainage pipe

 

Adopt suitable pipe diameter

 

Adopt nearby condensate water discharge

5.2  Key points of drainage water pipe 

installation

1. Considering the pipeline route and elevation.

 

Before installing condensate water pipeline, deter-
mine its route and elevation to avoid intersection 
with other pipelines and ensure slope is straight.

2. Drainage pipe selection

 

The drainage pipe diameter shall not small than the 
drain hose of indoor unit

 

According to the water flowrate and drainage pipe 
slope to choose the suitable pipe, the water flow-
rate is decided by the capacity of indoor unit.

Relationship between water flowrate and capacity of 
indoor unit

Capacity (kBtu)

Water flowrate (l/h)

12

2.4

18

4

24

6

36

8

48

12

55

14

According to the above table to calculate the total water 
flowrate for the confluence pipe selection.

For horizontal drainage pipe 

(The following table is for 

reference)

PVC 

pipe

Reference 

value of inner 

diameter of 

pipe (mm)

Allowable 

maximum water 

flowrate (l/h)

Remark

Slope 

1/50

Slope 

1/100

PVC25

20

39

27

For branch 

pipe

PVC32

25

70

50

PVC40

31

125

88

Could be used 
for confluence 

pipe

PVC50

40

247

175

PVC63

51

473

334

Attention: Adopt PVC40 or bigger pipe to be the main 
pipe.

For Vertical drainage pipe 

(The following table is for 

reference)

PVC 

pipe

Reference 

value of inner 

diameter of 

pipe (mm)

Allowable 

maximum water 

flowrate (l/h)

Remark

PVC25

20

220

For branch 

pipe

PVC32

25

410

PVC40

31

730

Could be 

used for 

confluence 

pipe

PVC50

40

1440

PVC63

51

2760

PVC75

67

5710

PVC90

77

8280

Attention: Adopt PVC40 or bigger pipe to be the main 
pipe.

3. Individual design of drainage pipe system

 

The drainage pipe of air conditioner shall be in-
stalled separately with other sewage pipe, rainwater 
pipe and drainage pipe in building.

 

The drainage pipe of the indoor unit with water 
pump should be apart from the one without water 
pump.

4. Supporter gap of drainage pipe

 

In general, the supporter gap of the drainage pipe 
horizontal pipe and vertical pipe is respectively 
1m~1.5m and 1.5m~2.0m. 

 

Each vertical pipe shall be equipped with not less 
than two hangers.

 

Overlarge hanger gap for horizontal pipe shall cre-
ate bending, thus leading to air block. 

5. The horizontal pipe layout should avoid converse flow or 
bad flow

Содержание KSD-35 DR14

Страница 1: ...KUE 35 DVR13 KSDA 52 DVR14 KSD 52 DR14 KUE 52 DVR13 Double Flow Console TECHNICAL MANUAL Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference ...

Страница 2: ...ight Difference 10 Noise Criterion Curves 11 Electrical Characteristics 2 Product Features 28 1 Operation Modes and Functions 2 Remote Controller Functions 3 Installation 34 1 Installation Overview 2 Location Selection 3 Indoor Unit Installation 4 Outdoor Unit Installation 5 Drainage Pipe Installation 6 Refrigerant Pipe Installation 7 Vacuum Drying and Leakage checking 8 Additional Refrigerant Cha...

Страница 3: ...Centre of Gravity 10 5 Electrical Wiring Diagrams 11 6 Refrigerant Cycle Diagrams 15 7 Air Velocity and Temperature Distributions 16 8 Capacity Tables 18 9 Capacity Correction Factor for Height Difference 24 10 Noise Criterion Curves 25 11 Electrical Characteristics 27 Specifications ...

Страница 4: ...e following table to determine the specific indoor and outdoor unit model number of your purchased equipment Indoor Unit Model Outdoor Unit Model Capacity Btu h Power Supply KSD 35 DR14 KUE 35 DVR13 12K 1Phase 220 240V 50Hz KSD 52 DR14 KUE 52 DVR13 18K ...

Страница 5: ...air flow Hi Mi Lo m3 h 650 580 490 780 690 600 Indoor sound pressure level dB A 37 34 27 41 38 32 Indoor sound power level dB A 54 55 Indoor unit Dimension W D H mm 794x206x621 794x206x621 Packing W D H mm 865x280x719 865x280x719 Net Gross weight Kg 14 9 18 8 14 9 18 8 Drainage water pipe diameter mm ODɸ16mm ODɸ16mm Refrigerant piping Liquid side Gas side mm inch ɸ6 35 ɸ9 52 1 4 3 8 ɸ6 35 ɸ12 7 1 ...

Страница 6: ...d quantity Kg 0 71 1 15 Design pressure MPa 4 3 1 7 4 3 1 7 Refrigerant piping Liquid side Gas side mm inch ɸ6 35 ɸ9 52 1 4 3 8 ɸ6 35 ɸ12 7 1 4 1 2 Max refrigerant pipe length m 25 30 Max difference in level m 10 20 Ambient temperature Cooling C 15 50 15 50 Heating C 15 24 15 24 Qty per 20 40 40 HQ Outdoor unit 132 264 352 114 234 312 Notes 1 Capacities are based on the following conditions Coolin...

Страница 7: ...Specifications Page 7 3 Dimensional Drawings 3 1 Indoor Unit ...

Страница 8: ...Specifications Page 8 3 2 Outdoor Unit KUE 35 DVR13 ...

Страница 9: ...Specifications Page 9 KUE 52 DVR13 ...

Страница 10: ...Specifications Page 10 4 Centre of Gravity KUE 35 DVR13 KUE 52 DVR13 ...

Страница 11: ...unit Abbreviation Paraphrase Y G Yellow Green Conductor CAP1 Indoor Fan Capacitor FAN Indoor Fan PUMP PUMP L LIVE N NEUTRAL TO CCM Comm Bus Central Controller T1 Indoor Room Temperature T2 Coil Temperature of Indoor Heat Exchanger P1 Super High Speed P2 High Speed ...

Страница 12: ...re controller To Remote Contol To Remote Alarm 3 YELLOW WHITE Y G RED N_IN BLACK INDOOR UNIT OUTDOOR UNIT 1 L 2 N L_IN S CN12CN42 INDOOR FAN2 M CN23 CN19 CN81 PLASMA LOWER OUTLET SWING MOTOR CN15 2 5 5 CN18 CN32 CN5 CN4 Humidity 5 CN1 CN3 CN43 CN40 CN46 CN45 CN44 16022700003468 This symbol indicates the elementis optional the actual shape shall prevail S T1 T2 M HB ROOMTEMP SENSOR PIPE TEMP SENSOR...

Страница 13: ... COMP Compressor L PRO K2 Low Pressure Switch Shorting Stub K1 High Pressure Switch Shorting Stub TRANS Power Transformer T4 10KΩ RESISTANCE Outdoor Ambient Temperature T3 10KΩ RESISTANCE Coil Temperature of Condenser XT1 2 Way Terminal 4 Way Terminal XT2 3 Way Terminal XT4 Terminal K3 Compressor Discharge Temperature Shorting Stub XP1 XP5 XT5 XT7 Connectors ...

Страница 14: ...Specifications Page 14 KUE 35 DVR13 KUE 52 DVR13 ...

Страница 15: ...le Diagrams Model Pipe Size Diameter ø mm inch Piping length m ft Elevation m ft Additional Refrigerant Gas Liquid Rated Max Rated Max 12k 9 52 3 8 6 35 1 4 5 16 4 25 82 0 10 32 8 12g m 0 13oz ft 18k 12 7 1 2 6 35 1 4 5 16 4 30 98 4 0 20 65 6 ...

Страница 16: ...Specifications Page 16 7 Air Velocity and Temperature Distributions Discharge Angle 70 Upper 0 Lower Cooling airflow velocity distributions Cooling temperature distributions ...

Страница 17: ...Specifications Page 17 Discharge Angle 20 Upper 0 Lower Heating airflow velocity distributions Heating temperature distributions ...

Страница 18: ... 90 3 90 3 90 4 19 4 19 4 19 4 19 S T 0 73 0 83 0 92 1 00 0 59 0 67 0 76 0 85 0 52 0 60 0 69 0 77 0 36 0 44 0 52 0 60 PI 0 70 0 70 0 70 0 70 0 69 0 69 0 69 0 69 0 69 0 69 0 69 0 69 0 69 0 69 0 69 0 69 20 TC 3 53 3 54 3 57 3 60 3 75 3 75 3 75 3 75 3 86 3 86 3 86 3 86 4 15 4 15 4 15 4 15 S T 0 73 0 83 0 92 1 00 0 59 0 67 0 76 0 85 0 52 0 60 0 69 0 77 0 36 0 44 0 52 0 60 PI 0 72 0 73 0 73 0 72 0 72 0...

Страница 19: ... 31 1 31 1 32 1 32 1 32 1 32 650 15 TC 3 84 3 87 3 90 3 93 4 02 4 02 4 02 4 05 4 12 4 12 4 12 4 12 4 40 4 40 4 40 4 40 S T 0 77 0 88 1 00 1 00 0 60 0 70 0 81 0 98 0 51 0 62 0 72 0 83 0 33 0 42 0 52 0 63 PI 0 70 0 70 0 70 0 70 0 69 0 69 0 69 0 69 0 69 0 69 0 69 0 69 0 69 0 69 0 69 0 69 10 TC 3 82 3 85 3 88 3 91 3 99 3 99 3 99 4 02 4 10 4 10 4 10 4 10 4 38 4 38 4 38 4 38 S T 0 78 0 88 1 00 1 00 0 60...

Страница 20: ... 22 4 22 4 22 4 22 S T 0 78 0 89 1 00 1 00 0 61 0 72 0 82 0 93 0 53 0 63 0 74 0 84 0 34 0 44 0 53 0 63 PI 1 90 1 90 1 90 1 90 1 91 1 91 1 91 1 91 1 91 1 91 1 91 1 91 1 93 1 93 1 93 1 93 690 15 TC 5 35 5 35 5 41 5 47 5 60 5 60 5 60 5 60 5 76 5 76 5 76 5 76 6 10 6 10 6 10 6 10 S T 0 70 0 79 0 98 1 00 0 56 0 65 0 73 0 81 0 50 0 58 0 66 0 74 0 35 0 42 0 49 0 57 PI 1 02 1 02 1 02 1 02 1 01 1 01 1 01 1 ...

Страница 21: ... 08 1 08 1 09 1 09 1 09 1 09 20 TC 5 18 5 18 5 24 5 30 5 50 5 50 5 50 5 50 5 64 5 64 5 64 5 64 6 08 6 08 6 08 6 08 S T 0 75 0 85 0 95 1 00 0 59 0 69 0 79 0 88 0 52 0 61 0 71 0 80 0 35 0 44 0 52 0 61 PI 1 13 1 13 1 13 1 13 1 13 1 13 1 13 1 13 1 12 1 12 1 12 1 12 1 12 1 12 1 12 1 12 25 TC 4 92 4 92 4 98 5 04 5 24 5 24 5 24 5 30 5 41 5 41 5 41 5 41 5 82 5 82 5 82 5 82 S T 0 77 0 87 0 97 1 00 0 60 0 7...

Страница 22: ...0 7 0 3 17 3 14 3 12 3 12 1 36 1 41 1 38 1 38 5 6 3 21 3 18 3 16 3 16 1 32 1 33 1 33 1 34 2 8 3 24 3 21 3 18 3 18 1 24 1 25 1 25 1 26 0 0 3 24 3 21 3 18 3 16 1 18 1 18 1 18 1 18 2 8 3 36 3 30 3 27 3 27 1 11 1 11 1 11 1 11 5 6 3 56 3 53 3 50 3 47 1 05 1 04 1 04 1 04 7 0 3 81 3 78 3 72 3 69 1 01 0 97 1 00 1 00 11 1 3 96 3 90 3 87 3 84 0 91 0 90 0 89 0 89 13 9 4 07 4 01 3 98 3 96 0 84 0 82 0 82 0 81 ...

Страница 23: ...4 89 4 86 4 84 4 81 1 79 1 85 1 83 1 84 5 6 4 87 4 84 4 81 4 78 1 75 1 77 1 78 1 79 2 8 4 84 4 78 4 75 4 75 1 68 1 70 1 70 1 71 0 0 4 75 4 69 4 66 4 63 1 60 1 62 1 62 1 63 2 8 4 81 4 75 4 72 4 69 1 54 1 55 1 56 1 57 5 6 5 04 4 95 4 92 4 89 1 48 1 49 1 50 1 50 7 0 5 31 5 22 5 19 5 13 1 47 1 44 1 48 1 48 11 1 5 36 5 30 5 25 5 22 1 37 1 37 1 37 1 37 13 9 5 42 5 36 5 30 5 28 1 30 1 30 1 30 1 30 16 7 5...

Страница 24: ...78 0 970 0 1 000 0 993 0 978 0 970 Outdoor Upper than Indoor 5 0 992 0 985 0 970 0 962 10 0 977 0 962 0 955 Capacity Btu h 18K Pipe Length m Cooling 5 10 20 30 Height difference H m Indoor Upper than Outdoor 20 0 928 0 912 10 0 969 0 937 0 921 5 0 995 0 979 0 946 0 930 0 1 000 0 984 0 951 0 935 Outdoor Upper than Indoor 5 1 000 0 984 0 951 0 935 10 0 984 0 951 0 935 20 0 951 0 935 Heating 5 10 20 ...

Страница 25: ...alid at free field condition Data is valid at nominal operation condition Reference acoustic pressure OdB 20µPa Sound level will vary depending on a range of factors such as theconstruction acousticabsorptioncoefficient ofparticular room in which the equipment is installed The operating conditions are assumed to be standard KSD 35 DR14 KSD 52 DR14 ...

Страница 26: ... at free field condition Data is valid at nominal operation condition Reference acoustic pressure OdB 20µPa Sound level will vary depending on arrange off actors such as the construction acoustic absorption coefficient of particular room in which the equipment is installed The operating conditions are assumed to be standard KUE 35 DVR13 KUE 52 DVR13 ...

Страница 27: ...240V 50Hz 220 240V 50Hz Power Wiring mm2 3 1 5 3 2 5 Circuit Breaker Fuse A 20 16 20 16 Indoor Outdoor Connecting Wiring Weak Electric Signal mm2 Strong Electric Signal mm2 4 1 0 4x2 5 with auxiliary electric heater 4 1 0 4x2 5 with auxiliary electric heater NOTE Electric auxiliary heating type circuit breaker fuse need to add more than 10 A ...

Страница 28: ...9 1 6 Heating Mode Heat pump models 30 1 7 Auto Mode 32 1 8 Drying Mode 32 1 9 Forced operation Function 32 1 10 Timer Function 32 1 11 Sleep Function 32 1 12 Auto Restart 33 1 13 8 C Heating 33 1 14 Follow Me 33 1 15 Silence 33 1 16 ECO 33 1 17 Electrical energy consumption control function 33 1 18 Active Clean function 33 Product Features ...

Страница 29: ...s operation Inverter module protection The inverter module has an automatic shutoff mechanism based on the unit s current voltage and temperature If automatic shutoff is initiated the corresponding error code is displayed on the indoor unit and the unit ceases operation Indoor fan delayed operation When the unit starts the louver is automatically activated and the indoor fan will operate after a p...

Страница 30: ... protective time Compressor running frequency is more than test frequency When compressor running frequency is equal to test frequency T4 is more than 15 C or T4 fault Change setting temperature Turbo or sleep function on off Various frequency limit shutdown occurs 1 5 2 Indoor Fan Control 1 In cooling mode the indoor fan operates continuously The fan speed can be set to 1 100 or low medium high a...

Страница 31: ...mpressor to cease operations 1 6 2 Indoor Fan Control 1 In heating mode the indoor fan operates continuously The fan speed can be set to 1 100 or low medium high and auto Anti cold air function The indoor fan is controlled by the indoor temperature T1 and indoor unit coil temperature T2 ΔTE1 0 2 Auto fan action in heating mode Rise curve When T1 Tsc is higher than 1 5 C fan speed reduces to 80 Whe...

Страница 32: ...ling mode All protections are activated and operate the same as they do that in cooling mode Low Room Temperature Protection If the room temperature is lower than 10 C the compressor ceases operations and does not resume until room temperature exceeds 12 C 1 9 Forced Operation Function Press the AUTO COOL button the AC will run as below sequence Forced auto Forced cooling Off Forced cooling mode T...

Страница 33: ...s not receive a signal for 7 minutes or you press Follow Me the function turns off The unit regulates temperature based on its own sensor and settings 1 15 Silence Press Silence on the remote control to enable the SILENCE function While this function is active the compressor frequency is maintained at a lower level than F3 The indoor unit will run at faint breeze 1 which reduces noise to the lowes...

Страница 34: ...nstallation 39 4 Outdoor Unit Installation 41 5 Drainage Pipe Installation 42 6 Refrigerant Pipe Installation 43 7 Vacuum Drying and Leakage Checking 44 8 Additional Refrigerant Charge 45 9 Engineering of Insulation 46 10 Engineering of Electrical Wiring 47 11 Test Operation 47 Installation ...

Страница 35: ...tion sheath some models 2 Heat insulation pipe 1 Anchor 6 depending on models Mounting plate fixing screw 6 depending on models Copper nut 2 Hook 2 Drain joint some models 1 Seal ring some models 1 Magnetic ring wrap the electric wires S1 S2 P Q E around the magnetic ring twice 1 Magnetic ring Hitch on the connective cable between the indoor unit and outdoor unit after installation some models 1 ...

Страница 36: ...nstalled on the outdoor unit 1 on some models Transfer connector Φ9 52 Φ12 7 Φ0 375in Φ0 5in Packed with the indoor unit NOTE Pipe size may differ from appliance to appliance To meet different pipe size requirements sometimes the pipe connections need a transfer connector installed on the outdoor unit 1 on some models Red short connected wire Applied to the W L pin of outdoor unit terminal block b...

Страница 37: ...allation Overview Installation Order Install the drainpipe Install the outdoor unit 1 2 3 4 5 MC MC 6 7 Install the indoor unit Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes Perform a test run ...

Страница 38: ...irtight rooms Be sure to keep the unit unobstructed in at least two of the three directions M N P 2 4 Rows of series installation The relations between H A and L are as follows L A L H L 1 2H 25 cm 9 8 or more 1 2H L H 30 cm 11 8 or more L H Can not be installed L H 300 cm 118 or more A 60 cm 23 6 or more 150 cm 59 or more 25 cm 9 8 or more 25 cm 9 8 or more DO NOT install the rows of series like ...

Страница 39: ...tions it is not necessary 2 Fix the mounting plate with a tapping screw onto the wall NOTE It is recommended to fx it on the wall according to the hanging hole indicated by the arrow on the mounting plate Mounting plate must be installed horizontally Mounting plate Tapping screw Washer 6mm 3 Hang the indoor unit on the mounting plate The bottom of body can touch the floor or remain sus pended but ...

Страница 40: ... pipe 1 Open the bottom piping cover plate Press and hold the bottom two buckles and then rotate to open the piping cover plate Two buckles 2 Remove the cover plate Remove the pipe cover plate and install the internal and external connecting pipes NOTE Install small size piping first and then large size piping NOTE All the figures in this manual are for demonstration purposes only The air conditio...

Страница 41: ...avity center of the unit is not at its physical center so please be careful when lifting it with a sling Never hold the inlet of the outdoor unit to prevent it from deforming Do not touch the fan with hands or other objects Do not lean it more than 45 and do not lay it sidelong Make concrete foundation according to the specifications of the outdoor units Fasten the feet of this unit with bolts fir...

Страница 42: ...s for reference PVC pipe Reference value of inner diameter of pipe mm Allowable maximum water flowrate l h Remark Slope 1 50 Slope 1 100 PVC25 20 39 27 For branch pipe PVC32 25 70 50 PVC40 31 125 88 Could be used for confluence pipe PVC50 40 247 175 PVC63 51 473 334 Attention Adopt PVC40 or bigger pipe to be the main pipe For Vertical drainage pipe The following table is for reference PVC pipe Ref...

Страница 43: ...tact with ground directly 5 3 Insulation work of drainage pipe Refer the introduction to the insulation engineering parts 6 Refrigerant Pipe Installation 6 1 Maximum length and drop height Ensure that the length of the refrigerant pipe the number of bends and the drop height between the indoor and outdoor units meets the requirements shown in the following table Capacity kBtu h Max Length m ft Max...

Страница 44: ...rdinary vacuum drying 1 When conduct first vacuum drying connect pressure gauge to the infusing mouth of gas pipe and liquid pipe 4 Cut the selected pipe with pipe cutter Make the section flat and smooth 5 Insulate the copper pipe Before test operation the joint parts should not be heat insulated 6 Flare the pipe Insert a flare nut into the pipe before flaring the pipe According to the following t...

Страница 45: ...alf an hour If the pressure reached 755mmHg start to pressure leakage test If it cannot reached the value repeat vacuum damage and vacuum drying again for 1 hour 4 Leakage test After the vacuum degree reaches 755mmHg stop vacuum drying and keep the pressure for 1 hour If the indicator of vacuum gauge does not go up it is qualified If going up it indicates that there is moisture or leak source 8 Ad...

Страница 46: ...pipe shall be 5 10cm longer than the gap of the insulation mate rial The insulation material at the joint pipe shall be inserted into the gap of the insulation material The insulation material at the joint pipe shall be banded to the gap pipe and liquid pipe tightly The linking part should be use glue to paste to gether Be sure not bind the insulation material over tight it may extrude out the air...

Страница 47: ... 10 1 10 16 1 5 16 25 2 5 25 32 4 32 45 6 11 Test Operation 11 1 The test operation must be carried out after the entire installation has been completed 11 2 Please confirm the following points before the test operation The indoor unit and outdoor unit are installed prop erly Tubing and wiring are correctly completed The refrigerant pipe system is leakage checked The drainage is unimpeded The grou...

Страница 48: ...Turn on the main power switch and run the air conditioner in COOL mode d Listen to the sound of the drain pump to see if it makes any unusual noises e Check to see that the water is discharged It may take up to one minute before the unit begins to drain depending on the drainpipe f Make sure that there are no leaks in any of the piping g Stop the air conditioner Turn off the main power switch and ...

Страница 49: ......

Отзывы: