DC Inverter Chiller
48
3.3.2
Installation of multi-module water system pipeline
Figure 3-3.4: Installation of multi-module water system pipeline
Pump
No.n module
No.(n-1) address
No.1 module
No.(n-1) module
No.(n-2) address
No.0 address
Drill dead hole at the
position, and move the
total effluent temperature
sensor at No.0 address to
the position
Note: n: the module quantity, max
4
3.3.3
Diameter parameters of main inlet and outlet pipes
Table 3-3.5: Fouling factor
Cooling capacity
Total inlet and outlet water pipe
inside nominal diameter
15≤ Q≤ 30
DN40
30< Q≤ 90
DN50
90<Q≤ 130
DN65
130< Q≤ 210
DN80
210< Q≤ 325
DN100
325< Q≤ 510
DN125
510< Q≤ 740
DN150
740< Q≤ 1300
DN200
740< Q≤ 2080
DN250
Please pay attention to the following items when installing multiple modules:
Each module corresponds to an address code which cannot be repeated.
Main water outlet temperature sensing bulb and auxiliary electric heater are under control of the main module.
The unit can be started up through the wired controller only after all addresses are set and the aforementioned items
are determined. The wired controller is ≤500m away from the outdoor unit.
3.3.4
Chiller water flow
Minimum chilled water flow: if the system flow is less than the minimum unit flow rate, the evaporator flow can be
recirculated, as shown in the diagram below.
Figure 3-3.5: Diagram for minimum chilled water flow
Evaporator
Recirculation