DC Inverter Chiller
43
Table 3-2.1: Recommend minimum spacing
Module
Installation space (mm)
A
B
C
D
E
F
G
KEM-30 DRS4
KEM-30 DRS4 KH
≥800
≥2000
≥2000
≥800
≥800
≥1100
≥6000
KEM-60 DRS4
KEM-60 DRS4 KH
2.7
Installation of Damping Devices
2.7.1
Damping devices must be provided between the unit and its foundation
By means of the installation holes on the steel frame of the unit base, the unit can be fastened on the foundation
through the spring damper. See figure above (Figure 3-2.2) for details about center distance of the installation holes. The
damper does not go with the unit, and the user can select the damper according to the relevant requirements. When the
unit is installed on the high roof or the area sensitive to vibration, please consult the technical engineers before selecting
the damper.
2.7.2
Installation steps of the damper
Step 1. Make sure that the flatness of the concrete foundation is within ±3mm, and then place the unit on the
cushion block.
Step 2. Raise the unit to the height suitable for installation of the damping device. Remove the clamp nuts of the
damper.
Step 3. Place the unit on the damper, and align the fixing bolt holes of the damper with the fixing holes on the unit
base.
Step 4. Return the clamp nuts of the damper to the fixing holes on the unit base, and tighten them into the damper.
Step 5. Adjust the operational height of the damper base, and screw down the leveling bolts. Tighten the bolts by
one circle to ensure equal height adjustment variance of the damper.
Step 6. The lock bolts can be tightened after the correct operational height is reached.
Figure 3-2.5: Installation of the damper
Damping device
Anchor bolt M12
Nut
Ferrol
Fixed meatal
plate