Table 2-1.2: Specifications
(continued)
Expansion tank
Volume
L
4.2
12
Precharge pressure
Mpa
0.15
0.15
Test pressure
Mpa
1.0
1.0
Water flow switch
Action flow
m
3
/h
3.6± 10%
7± 10%
Vent Valve
Max working pressure
Mpa
1.0
1.0
Safety valve
Action pressure
Mpa
0.6 ± 10%
0.6 ± 10%
Controller
KCCHT-05 MODBUS
KCCHT-05 MODBUS
Operating temperature
range
Cooling
°C
-10 to 43
-10 to 43
Heating
°C
-14 to 30
-14 to 30
Water outlet
temperature range
Cooling
4
°C
0 to 20
*5
0 to 20
*5
Heating
°C
25 to 54
25 to 54
Notes:
1. Cooling: Chilled water inlet/outlet temp.12/7°C; outdoor ambient temp. 35°C DB.
2. Heating: Warm water inlet/outlet temp. 40/45°C; outdoor ambient temp. 7°C DB/6°C WB.
3. Sound pressure level is measured at a position 1m in front of the unit and 1.1m above the floor in a semi-anechoic chamber.
4. Capacity and efficiency data calculated in accordance with EN14511, EN14825
5. Cooling outlet water temperature from 0 to 5°C didn’t justify by Quality Control department. If you have such requirement, Please inform your supplier.