Part 3 - Ins
talla
tion and Field Se
ttings
DC Inverter Chiller
63
When set address "01-15" and press "OK" button, the wired controller will enter the interface as follows.
Figure 3-7.6: Main page for slave wired controller
MON
20/11/2017
PRESS MENU TO QUERY STATUS
ON
ONLINE
UNITES
16
10:35 A
COOL Tws
Tw
55
C
55
C
ERROR
E1
60%
45%
T5
55
C
7.2.8
Upper Computer Communication Function
1) The home page displays the content below during communication with the upper computer: Communication between
the wired controller and the upper computer.
2) If the outdoor main control board is in the remote ON/OFF control mode and the wired controller sends an alarm,
the current alarm page displays: Remote ON/OFF Control Mode. In this case, the network control of upper computer is
invalid, and the wired controller can query the system status only and cannot send out control information.