23
Follow these instructions to prevent distortion
when the compressor starts:
•
The unit must be connected to the main
outlet. Normally, the power supply must
have a low output impedance of 32 ohms.
•
No other equipment should be connected
to the same power circuit.
•
The
unit’s
power information can be found
on the rating sticker on the product.
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board(PCB) is
designed with a fuse to provide overcurrent
protection. The specifications of the fuse are
printed on the circuit board, such as:
Indoor unit:
T3.15A/250VAC, T5A/250VAC.
(applicable for unit adopts R32
refrigerant
only
)
Outdoor unit:
T20A/250VAC (for <24000Btu/h
unit), T30A/250VAC(for >24000Btu/h unit)
1.
Prepare the cable for connection
a.
You must first choose the right cable size
before preparing it for connection. Be sure
to use H07RN-F cables.
Table 8.1: Minimum Cross-Sectional Area
of Power and Signal Cables North America
Rated Current of
Appliance (A)
AWG
7
18
7 - 13
16
13 - 18
14
18 - 25
12
25 - 30
10
Wiring
NOTE:
The fuse is made of ceramic.
WARNING
Outdoor Unit Wiring
WARNING
DO NOT
modify the length of the power
cord or use an extension cord.
Safety Precautions
W
iri
ng
CAUTION
•
Connect the outdoor wires before
connecting the indoor wires.
•
Make sure you ground the unit. The
grounding wire should be away from gas
pipes, water pipes, lightning rods,
telephone or other grounding wires.
Improper grounding may cause electrical
shock.
•
DO NOT
connect the unit with the power
source until all wiring and piping is
completed.
•
Make sure that you do not cross your
electrical wiring with your signal wiring, as
this can cause distortion and interference.