![Kaysun COMPAK KHP 15/190 ACS1 Скачать руководство пользователя страница 39](http://html.mh-extra.com/html/kaysun/compak-khp-15-190-acs1/compak-khp-15-190-acs1_technical-manual_659138039.webp)
Kaysun combo type KHP 15/190 ACS1 Manual MCAC-RTSM-2017-09
36
²
If press within 10 seconds, setting parameters will be uploaded to unit.
²
If press beyond 10 seconds, all the parameters should be reset.
²
If screen and buttons are locked, press it for 3 seconds to unlock them.
DISINFECT
Manually turn on disinfect function.
²
Press ‘
DISINFECT
’ button, the icon ‘
’ will flash.
²
Press ‘
ENTER
’ to confirm manually activate disinfection function. The unit will heat up water to
65°C at least for disinfection.
Disinfect clock setting
²
Press button ‘
DISINFECT
’ for 3 seconds to enter disinfect clock setting. Then icon ‘
’ will flash,
and icon ‘
’ will be lightened and the hour value of clock will flash slowly.
²
By pressing ‘
UP
’ or ‘
DOWN
’, set the hour value of clock.
²
Press ‘
CLOCK
’ button to confirm the hour setting. Then the minute value of clock will flash
slowly.
²
By pressing ‘
UP
’ or ‘
DOWN
’, set the minute value of clock.
²
Press ‘
ENTER
’ to confirm the disinfect clock setting and quit out.
Notes:
Unit will automatically start disinfect function at the above-set clock every 7 days.
If without disinfect clock setting, unit will automatically start disinfect function at 23:00 every 7 days.
If unit is off or under disinfect mode, press ‘
DISINFECT
’ will lead to show ‘
’ on the display.
VACATION
In vacation mode, the setting target water temperature is 15°C as default and ‘
’ will show the
remaining vacation days. On the last day of vacation, unit will automatically start disinfect function,
and automatically reset the target temperature to the last one before vacation.
If unit has already been under vacation mode or off, press the button of ‘
VACTION
’, then it will lead to
show invalid icon ‘
’ on the display.