TSM 2017-09 ………….. Kaysun combo type KHP 15/190 ACS1 Manual
17
①
Air inlet and outlet with duct A+B≤10m
②
Only air outlet with duct
A≤10m
It is recommended to install unit by this way in winter,
where there is other heat source in the room.
③
Only air inlet with duct
A≤10m
It is recommended to install unit by this way in
summer that could charge fresh air into room.
Duct description
Round duct
Rectangle duct
Dimension (mm)
Ф160
160×160
Straight-line pressure drop (Pa/m)
≤2
≤2
Straight-line length (m)
≤10
≤10
Bent pressure drop (Pa)
≤2
≤
2
Bent’s quantity
≤5
≤5
²
The duct’s resistance will decrease air-flow-rate, and capacity of unit will be decreased.
²
It is recommended to install the unit in the indoor space. It is not allow installing the unit at
the rainy space.
²
In terms of the unit connect with duct reaching to outdoor, and then a reliable water-resistant
measure must be conduct on the duct, to prevent water from dropping into internal of the
unit.
²
Filter should be installed at the unit inlet, if the air inlet is not connected with duct. In terms of
the unit with duct, filter should be put on the position of duct inlet.
Unit
Rain
Rain
Weather shed
Unit