TSM 2017-09 ………….. Kaysun combo type KHP 15/190 ACS1 Manual
31
TCO and ATCO
The power of compressor and E-heater will be automatically switch on or switch off by TCO and
ATCO.
If the water temperature is higher than 78°C, the ATOC will automatically shut off the power of the
compressor and E-heater, and turn it on if the temperature falls down below 68°C.
If the water temperature is higher than 85°C, the TOC will automatically shut off the power of the
compressor and E-heater, it should be re-turn manually.
Defrosting function
Conditions to activate defrosting cycle:
When T3 ≤0 , Compressor is continually running for 40minutes. (For each start cycle, system will
count accumulated running time, when accumulated running time reaches 40 minutes defrosting
cycle will activate 2 minutes after Compressor’s next start)
Conditions to inactivate defrosting cycle: Defrosting time reaches 10 minutes or T3≥15°C.
Main components’ movement when defrosting
Auto-restart function
If electricity power failed, unit can memorize all setting parameters, and unit will be back to the
previous setting when power recovers.
Button auto-lock
When there is no operation of button for 1 minute, button except unlock button (‘
ENTER
’) will be
locked. Press ‘
ENTER
’ for 3 seconds, unlock buttons.
Screen auto-lock
If there is no operation of button for 30 seconds, screen will be locked (extinguished) except for error
code and alarm light. Press any button will unlock the screen (lighten).