After rinsing with water, reassemble the activator by reversing the steps listed above.
15
Troubleshooting
ELECTRIC SHOCK!
Switch off the Mains Switch and disconnect the Mains connection
(230/120VAC) before conducting any work on the Elektro Katadyn System
.
15.1
Flow Low
Flow Low
Flow rate through EK below 0.5 m^3/h
•
Check if water is available
•
Check if the inlet and outlet valves are open
•
Check if there is any restriction in the pipe system
•
Check if the Flow Switch is wired correctly
•
Check if there are any mechanical damages to the Flow Switch
15.2
Voltage High
Voltage High
Voltage on the Activator is above 21.5 V DC.
•
Check if there is an open circuit form the Control Cabinet to the Activator
•
Check if the Anode(s) is (are) used up. No silver visible on the anode
•
Check if the conductivity of the water is according to the technical data in chapter 8
15.3
Voltage Low
Voltage Low
Voltage on the Activator is below 0.25 V DC.
•
Check if there is an short circuit form the Control Cabinet to the Activator
•
Check if the current setting is correct
•
Check if the conductivity of the water is according to the technical data in chapter 8
15.4
Temperature High
Temperature High
Cabinet temperature (internal) is above 45°C
•
Check if the Temperature Switch inside the Control Cabinet is set to 45°C
•
Check to verify if ambient temperature is
≤
40°C
15.5
Overvoltage
Overvoltage
Electrical circuit to the Activator is open
•
Check if there is an open circuit form the Control Cabinet to the Activator
•
Check if the conductivity of the water is according to the technical data in chapter 8
Содержание EK-24
Страница 1: ...ELECTRO KATADYN INSTRUCTION MANUAL EK 4 EK 24...
Страница 16: ...Katadyn Page 15 Change to the screen Alarm History Change to the screen Trend...
Страница 36: ...Katadyn Page 35 17 3 Dimensions EK 4 245 0 105 0 140 0 G 50 0 85 0 G 286 0 41 5 R 6 0 162 0 545 0 78 0 300 400...
Страница 37: ...Page 36 Katadyn 17 4 Dimensions EK 24 300 400 140 G 1 G 1 235 400 400 160 240 50 65...
Страница 41: ...Page 40 Katadyn 17 6 2 EK 24 Anode brown Cathode blue EK Control Cabinet X1 1 2 br bl...
Страница 42: ...Katadyn Page 41 18 CE declaration of conformity...