Page 25
Precondition:
Option “Flow measurement” is available (Katadyn Flow Sensor instead of Flow Switch) and
connected to -X3:21/22/23 (see attachment 17.5 Electrical connection). Setpoint has to be changed to
ppm on the Screen “Setting”.
Change from current (mA) to dose control (ppm).
ppm control only with option “Flow measurement”
possible.
Warning indication on the “Overview” Screen if flow rate
or dosage is out of range.
Numerical current (mA) Setpoint input.
If the option “Flow measurement” is activated and the
control is set to ppm, then the required dose* in ppm can
be set over the numerical input.
11.12
Start/Stop silver ion (Ag+) production
NOTE
Ensure that the water flow and the setpoint is in compliance with the required
specification.
11.12.1
Start/Stop Local
Precondition:
Control has to be set to LOCAL on the Screen “Setting.”
Switch ON the EK System locally
The controller will ramp up the actual value to the Setpoint.
Switch OFF locally the EK System.
11.12.2
Start/Stop Remote
Precondition:
Control has to be set to REMOTE on the Screen “Setting”
Potential free contact connected to -X3:14/15 (see attachment 17.5 Electrical connection)
Close the contact to start the system remotely.
Содержание EK-24
Страница 1: ...ELECTRO KATADYN INSTRUCTION MANUAL EK 4 EK 24...
Страница 16: ...Katadyn Page 15 Change to the screen Alarm History Change to the screen Trend...
Страница 36: ...Katadyn Page 35 17 3 Dimensions EK 4 245 0 105 0 140 0 G 50 0 85 0 G 286 0 41 5 R 6 0 162 0 545 0 78 0 300 400...
Страница 37: ...Page 36 Katadyn 17 4 Dimensions EK 24 300 400 140 G 1 G 1 235 400 400 160 240 50 65...
Страница 41: ...Page 40 Katadyn 17 6 2 EK 24 Anode brown Cathode blue EK Control Cabinet X1 1 2 br bl...
Страница 42: ...Katadyn Page 41 18 CE declaration of conformity...