manualshive.com logo in svg
background image

15 

 

 

 

The following is provided to help diagnose a probable source of trouble. It is a guideline only and may not show all causes for all 
problems. For additional troubleshooting help, contact your local distributor or visit kascomarine.com for additional guidance.  

Note:

 you may need to refer to your owners manual that was provided with your control panel for additional control panel settings and 

adjustments. 

 

“My Aerator trips the ground fault interrupter in the C

-25, C-85, or C-

95.” 

 

This is the most common symptom of several possible problems. To correctly diagnose the problem, you will need to collect more 
information. A Ground Fault Interrupter (GFI) breaker that trips can indicate an electrical service problem, water contamination in the 
unit and/or cord, bad breaker, control box problems, motor problems, etc. Try to find out the answers to these questions before you 
contact Kasco to narrow down the problem: 

 

How long does it take to trip the breaker?  

 

Does it always take the same amount of time to trip?  

 

How many times has it tripped?  

 

Has there been any electrical problems in the area recently?  

“My Aerator seems to run slowly.” 

 

This can also be a symptom of several possible problems. There could be an electrical problem where the unit is not getting the proper 
voltage. This could also indicate a problem with the motor of the unit, which needs to be looked at by an Authorized Repair Center. 
Check that the unit is receiving the proper voltage, and, if so, contact Kasco for further steps.  

“My Aerator hums, but will not start. When I spin the prop with a stick, it starts up.” 

 

(single phase units only) This indicated a problem with the Starting Capacitor. Each Kasco aerator is equipped with a Starting 
Capacitor to get the unit going when it is first plugged in. If it is operating, but not spinning and can be started by spinning the prop with 
a stick, the Starting capacitor needs to be replaced by an Authorized Repair Center.  

“My Aerator turns itself off and back on without the timer and without tripping the GFI breaker.” 

 

(single phase units only) Each Kasco aerator has a Thermal Overload built in that will turn the unit off when it overheats. Once the unit 
has cooled down, it will start back up. If you are noticing these symptoms, the unit should be unplugged immediately because the 
Thermal Overload will continue to turn on and off until it burns out and damages the motor. The unit should be unplugged and taken out 
of the water to find the cause of the problem. The problem could be one of many, such as, low water levels, build-up on the unit to 
prevent heat dissipation, something inhibiting the free rotation of the shaft, etc. If something is caught in the unit or there is a build-up of 
algae, calcium or organic matter on the unit, remove the debris and, if caught early enough, the unit should 22 be fine. Contact a Kasco 
representative before restarting the unit.  

“My Aerator flow seems to fluctuate and/or be less than usual.” 

 

This can occur because of a few different reasons. Most of the time, this symptom is caused from unit being clogged with debris. A mat 
of weeds, many leaves, plastic bags, etc. can clog up the unit and cause it to be starved of water. If the unit does not have the proper 
amount of water, the flow or pattern will fluctuate up and down and look sporadic. If you are seeing these symptoms, unplug the unit 
and clean away the debris that is clogging up the screen. Another possibility if these symptoms are noticed, is a chipped or damaged 
prop that is causing the unit to wobble and not pump properly. When the unit is unplugged, check the prop for damages and replace if 
damage is found.  

The GFI breaker trips randomly and sporadically. Sometimes it is a few hours of operation, other times it can be days or week

s.” 

 

Troubleshooting Tips 

Содержание VFX Series

Страница 1: ...1 Manual Number 884172 Owners Manual VFX Series Aerators 8400VFX 5 1VFX 2 3VFX 5 3VFX 2 3HVFX 5 3HVFX Kasco Marine Inc 800 Deere Rd Prescott WI 54021 PH 715 262 4488 kascomarine com Rev 5 2020...

Страница 2: ...r use with a GFCI receptacle Control panels MUST be installed by a qualified electrician Ground Fault Circuit Interrupters GFCIs should be tested upon each installation and every month thereafter to e...

Страница 3: ...arrier that will make the unit inaccessible to persons in the water A complete list of control panels can be found in the Accessories section of kascomarine com Additional Notes During flotation opera...

Страница 4: ...4 Unit Size H PartNo D PartNo 2hp 8400VFX 284102 2hp 3 phase 2 3VFX 284103 5hp 5 1VFX 284105 5hp 3 phase 5 3VFX 284105 Parts Included...

Страница 5: ...wrench Repeat for all three legs on the unit assembly Step 2 Place the float D over the unit assembly so that it rests on the L brackets Ensure the three channels on the inside of the float line up wi...

Страница 6: ...n C to the ledge on the top of the float using the 3 8 16 x 3 hex head screw A and 3 8 lock washer B through the hole in the L bracket using the 9 16 socket wrench Repeat for all three upper screen se...

Страница 7: ...the mesh screen L and wrap into a cone shape by overlapping both vertical edges by approximately 1 inch and aligning top and bottom edges of mesh as shown Secure mesh vertical seam at the top bottom...

Страница 8: ...the float allowing the unit power cord to exit between them in the dedicated channel Dedicated power cord channel Step 7 Flip mesh and screen assembly over and use remaining cable ties to secure mesh...

Страница 9: ...is between the two flanges on each clip as shown Tighten all three serrated hex head screws to secure the screen to the bottom of the float being sure not to pinch the power cord 9 16 socket or combin...

Страница 10: ...ignificantly a small weight may need to be suspended at the midpoint of the rope to take up any slack caused by a drop in water level 1 foot of 1 galvanized pipe works well The weight should be light...

Страница 11: ...lectrician 1 Verify all screw terminal connections are tightened to specified torque setting prior to energizing the panel 2 Verify the electrical service voltage and phase matches the control panel a...

Страница 12: ...od of time to ensure continued oil lubrication of seals units that sit upright for many months or years have a greater likelihood of seals drying out CLEANING Aerators should be removed from the water...

Страница 13: ...CONSEQUENTIAL DAMAGES Warranty is void if The aerator is not maintained properly according to the Maintenance Recommendations supplied in this Owner s Manual The aerator is returned for repair withou...

Страница 14: ...uthorized Repair Center or to Kasco at Kasco Marine Inc 800 Deere Rd Prescott WI 54021 Attn Repairs Non Warranty Repairs Most failed equipment can be repaired at substantially lower costs than replace...

Страница 15: ...but not spinning and can be started by spinning the prop with a stick the Starting capacitor needs to be replaced by an Authorized Repair Center My Aerator turns itself off and back on without the tim...

Страница 16: ...is placed It is caused by either induced current in the ground wire or a base voltage difference due to soil pH levels To resolve the problem contact an electrician and install a local grounding stake...

Страница 17: ...17 Replacement Parts Unit Size H PartNo D PartNo 2hp 8400VX 284102 2hp 3 phase 2 3VX 284103 5hp 5 1VX 284105 5hp 3 phase 5 3VX 284105...

Страница 18: ...18...

Страница 19: ...unit unless otherwise instructed A fee of 60 per hour will be assessed for cleaning excessively dirty units and float disassembly Refer to the Owner s manual for easy to follow troubleshooting rule ou...

Отзывы: