7.6
Installation examples (mechanical)
Both MULTICAL® 603 and MULTICAL® 803 (by means of mounting bracket 3026-857) can be mounted directly on
ULTRAFLOW® 54/34. To optimize the readability of the calculator display, you can benefit from using the supplied angle
bracket 3026-858 for ULTRAFLOW® 54 (type 65-5-XXHX-XXX).
Note: At medium temperatures above 90 °C or below the ambient temperature, calculator and Pulse Transmitter/Pulse
Divider must not be mounted on the flow sensor. Instead wall-mounting is recommended.
7.6.1
MULTICAL® 603 mounted on ULTRAFLOW® 54 (Type 65-5-XXHX-XXX)
7.6.1.1
Installation in an ascending pipe
Figure 21. MULTICAL® 603 mounted on ULTRAFLOW® 54 mounted in an ascending pipe.
When installing ULTRAFLOW® in an ascending pipe, it can be of advantage to turn ULTRAFLOW® ±360° around the pipe
axis to optimize the readability of the MULTICAL® display at direct mounting of MULTICAL® on ULTRAFLOW®.
7.6.1.2
Installations at or above eye level
Figure 22. MULTICAL® 603 mounted on ULTRAFLOW® 54 mounted horizontally at or above eye level.
In case of installation above eye level, it can be of advantage to turn ULTRAFLOW® 54 -45° downwards to optimize the
readability of the MULTICAL® display at direct mounting of MULTICAL® on ULTRAFLOW®.
Note: At installation in humid environments, the plastic housing of ULTRAFLOW® 54 (type 65-5-XXHX-XXX) must be
positioned on the side (at horizontal mounting).