MULTICAL® 801
Kamstrup A/S · Technical Description · 5512-571_R1_GB _11.2016
97
11.2
Retrofitting modules
Modules for MULTICAL
801 are also supplied separately for retrofitting. The modules are configured and ready for
installation from the factory. However, some of the modules need individual configuration after installation, which
is possible by means of METERTOOL.
Module 1 (Module 2)
Possible configuration after installation
M-Bus + pulse inputs
20
(V)
Pulse values of VA and VB are changed via METERTOOL.
Primary and secondary M-Bus addresses can be changed via
METERTOOL or M-Bus. Furthermore, monthly logger data can
be selected instead of yearly logger data via M-bus.
RadioRouter + pulse inputs
21
(W)
Pulse values of VA and VB are changed via METERTOOL.
Prog. data RTC + 4…20 mA
pulse inputs
22
-
Clock adjustment.
Pulse values of VA and VB are changed via METERTOOL.
LonWorks, FTT-10A + pulse inputs
24
(Y)
Pulse values of VA and VB are changed via METERTOOL. All
other configurations are made via LonWorks.
M-Bus module with alternative reg pulse
inputs
27
(P)
Pulse values of VA and VB are changed via METERTOOL.
Primary and secondary M-Bus addresses can be changed via
METERTOOL or M-Bus. Furthermore, monthly logger data can
be selected instead of yearly logger data via M-Bus
M-Bus module with MC-III data p pulse
inputs
29
(Q)
Pulse values of VA and VB are changed via METERTOOL.
Primary and secondary M-Bus addresses can be changed via
METERTOOL or M-Bus.
Wireless M-Bus + pulse inputs
30/35/38
Pulse values of VA and VB are changed via METERTOOL
Wireless M-Bus
31
N/A
ZigBee 2.4 GHz internal a pulse inputs
60
Pulse values of VA and VB are changed via METERTOOL
Metasys N2 (RS485) + pulse inputs
62
Pulse values of VA and VB are changed via METERTOOL
SIOX module
64
(M)
N/A
BACnet MS/TP + pulse inputs
66
Configuration of communication address via Module
Programmer or METERTOOL.
Modbus RTU + pulse inputs
67
Configuration of communication address etc. via Module
Programmer or METERTOOL.
High Power Radio pulse inputs
84
Pulse values of VA and VB are changed via METERTOOL