6.10.4
Info event counter
Info event counter
Increment with each change of the info code.
The info event counter of a new meter will be 0 as
“transport mode” prevents counting during
transportation.
Info code
”info” in
display
Registration in info, daily,
monthly or yearly logger
Counting of Info event
1
Yes
Yes
With each “main power” On/Off
4, 8, 32
Yes
Yes
When Info 4, 8, 32 is set or removed.
Max. 1 per temperature measurement
64, 256
Yes
Yes
When Info is set and when Info is
deleted.
Max. once a day
512
Yes
Yes
When Info is set and when Info is
deleted.
Max. once every 120 s.
16, 128, 1024, 2048,
4096, 8192, 16384, 32768
Yes
Yes
When Info is set and when Info is
deleted.
Max. once a day