MULTICAL® 801
52
Kamstrup A/S · Technical Description · 5512-571_R1_GB_11_2016
6.10.2
Info code types
Info Code
Description
Response time
0
No irregularities
-
1
Supply voltage has been interrupted
-
8
Temperature sensor T1 outside measuring
range
1…10 min
4
Temperature sensor T2 outside measuring
range
1…10 min
32
Temperature sensor T3 outside measuring
range
1…10 min
64
Leak in cold water system
24 hours
256
Leak in heating system
24 hours
512
Burst in heating system
120 s.
ULTRAFLOW
®
X4 info (activated when CCC=4XX)
16
Flow meter V1 communication error
After reset and 24 hours (at 00:00)
1024
Flow meter V2 communication error
After reset and 24 hours (at 00:00)
2048
Flow meter V1 wrong pulse figure
After reset and 24 hours (at 00:00)
128
Flow meter V2 wrong pulse figure
After reset and 24 hours (at 00:00)
4096
Flow meter V1, signal too weak (air)
After reset and 24 hours (at 00:00)
8192
Flow meter V2, signal too weak (air)
After reset and 24 hours (at 00:00)
16384
Flow meter V1 wrong flow direction
After reset and 24 hours (at 00:00)
32768
Flow meter V2 wrong flow direction
After reset and 24 hours (at 00:00)
If several info codes appear at the same time, the sum of the info codes is displayed. If e.g. both temperature
sensors are outside measuring range, info code 12 is displayed.
During factory configuration, the individual info codes are set active or passive, meaning that a standard heat meter
that does not use T3 cannot set info code 32.
Info = 16-1024-2048-128-4096-8192-16384-32768 functions via data communication between MULTICAL
®
and
ULTRAFLOW
®
54. See paragraph14.2.5, Info code setup, in order to change the settings.
6.10.3
Transport mode
When the meter leaves the factory it is in transport mode, whereby the info codes are active in the display only, not
in the data logger. This prevents ”infoevent” from counting during transportation and non-relevant data from
appearing in the info logger. When the meter has accumulated the volume register the first time after the
installation, the info code automatically becomes active.