9
Kamstrup A/S • 55121068_B3_GB_03.2015
MULTICAL® 62 • Water meter
5.1.6
Lon Works + pulse inputs, type 67-00-24
The LonWorks module is used for data transfer from MULTICAL® 62 either for data reading/registra-
tion or regulation purposes via the Lon-Bus.
The module must be powered by 24 VAC.
A list of network variables (SNVT) and further details about the LonWorks module appear from data
sheet. Regarding mounting we refer to installation instructions 5512-396.
See installation instructions 5512-396 (DK) or 5512-403 (GB).
5.1.7
Wireless M-Bus + 2 pulse inputs, type 67-00-30
The radio module has been designed to form part of the hand-held Wireless M-Bus Reader sys-
tems of Kamstrup A/S at license-free radio frequency (868 MHz).
The module fulils the C-mode speciications of prEN13757-4 and can thus form part of other
systems using Wireless M-Bus C-mode communication.
The radio module comes with internal antenna and external antenna connection as well as two
pulse inputs, which are identical to the previously described pulse inputs.
The Wireless M-Bus radio transmitter is switched off on dispatch from the factory. It turns on
automatically when one liter of water has run through the meter. The radio transmitter can also be
switched on by means of a forced dial-up to the meter (keep both front keys pressed for approx.
5 secs. until CALL is displayed).
5.1.8
2 pulse inputs, type 67-00-60
The ZigBee module is mounted direct in the meter and is powered by the meter’s supply. The
module operates within the 2.4 GHz area and is ZigBee Smart Energy certiied. The certiication
secures that the meter can form part of other ZigBee networks, e.g. reading several meter types
from different meter suppliers.
To be able to offer a compact solution the module uses an internal antenna.
5.1.9
Metasys N2 (RS485) + N2 (RS485) + 2 pulse inputs, type 67-00-62
The N2 module is used for data transfer from MULTICAL® water meters to an N2 Master in a
Johnson Controls System. The N2 module transfers accumulated volume and low to an N2 Master.
N2 Open from Johnson Controls is a widespread and established ield bus protocol used within
building automation. The N2 module for MULTICAL® 62 ensures simple integration from Kamstrup’s
water meters to N2 Open based systems. Address area is 1-255 determined by the last three digits
of the meters customer number.
5.1.10 SIOX module (Auto detect Baud rate), type 602-00-64
SIOX is used for data reading of small and medium-sized groups of water meters via cable, the
data readings being presented by the main system, e.g. MCom, Fix or Telefrang. Further informa-
tion on these systems can be ordered from the supplier of these. Furthermore, a coniguration tool
is available from Telefrang.
The two-wire serial SIOX bus connection is optoisolated from the meter and is connected without
regard to polarity (i.e. the polarity is unimportant). The module is powered by the SIOX bus. Commu-
nication speed between 300 and 19,200 baud. The module automatically uses the highest possible
communication speed. The module converts data from KMP protocol to SIOX protocol.